Datasheet excerpt: Technical data of 
KFA6-SR2-Ex1.W

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 14, 15
Rated voltage 207 … 253 V AC, 45 … 65 Hz
Power dissipation 1 W
Power consumption max. 1 W
Input
Connection side field side
Connection terminals 1+, 2+, 3-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 … 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
Output
Connection side control side
Connection terminals 7, 8, 9
Output signal ; relay
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency < 10 Hz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LEDs
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate PTB 00 ATEX 2081
Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input Ex ia
Voltage 10.6 V
Current 19.1 mA
Power 51 mW (linear characteristic)
Supply
Maximum safe voltage 253 V AC (Attention! Um is no rated voltage.)
Output
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Maximum safe voltage 253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
International approvals
FM approval
Control drawing 116-0035
UL approval
Control drawing 116-0145
CSA approval
Control drawing 116-0047
IECEx approval
IECEx certificate IECEx PTB 11.0031
IECEx marking [Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

System Classcode
ECLASS 13.0 27210121
ECLASS 12.0 27210121
ECLASS 11.0 27210121
ECLASS 10.0.1 27210121
ECLASS 9.0 27210121
ECLASS 8.0 27210121
ECLASS 5.1 27210121
ETIM 9.0 EC001485
ETIM 8.0 EC001485
ETIM 7.0 EC001485
ETIM 6.0 EC001485
ETIM 5.0 EC001485
UNSPSC 12.1 32101514

Details:
KFA6-SR2-Ex1.W

Function

This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.

The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The barrier output changes state when the input signal changes state. The normal output state can be reversed using switch S1. Switch S3 is used to enable or disable line fault detection of the field circuit.

During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.

Associated Products:
KFA6-SR2-Ex1.W

Matching System Components

  • K-DUCT-BU
  • Profile Rail

Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aids
Accessories

  • F-NR3-Ex1
  • NAMUR Resistor Network

1-channel, Dry contact input, For line fault detection (LFD)

  • KF-ST-5GN
  • Terminal Block

3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces green

  • KF-ST-5BU
  • Terminal Block

3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces blue

  • KF-CP
  • Coding Pins

Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pins

Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.

background image

1

103

37

4_

EN

G.xm

l

2

003

-03-

2

5

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

KFA6-SR2-Ex1.W

Isolated switch amplifiers

yellow

green

Output

Power

supply

Saf

e area

Input I EEx ia IIC

Switch S3 in position I

Switch S3 in position I

Switch S3 in position I

Switch S3 in position II

Hazar

dous area

LB

SC

red

Power

Rail

LB/SC
collective
error message

only
KFD2-SR2-Ex1.W

without LB, SC

without SC

&

3-

1+

7

8

9

S1

14 15

+

+

2+

II

I

1+

3-

1+

3-

3-

2+

3-

1+

10 k

10 k

400

Ω ≤ R ≤ 2 kΩ

S3

Composition

230 V AC
• 1-channel

• Control circuit EEx ia IIC

• Reversible mode of operation

• 1 relay output with 1 changeover

contact

• EMC acc. to NAMUR NE 21

• LB/SC monitoring

• Usable up to SIL 2 acc. to IEC 61508

The transformer isolated barrier
transfers digital signals from the
hazardous area. Sensors per
DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as
alarms. Control circuits are monitored
for lead breakage (LB) and short circuit
(SC). The external faults are indicated
according to NAMUR NE44 by a red
flashing LED. For type KFD2-SR2-
Ex1.W, an LB/SC collective error
message is in addition transferred
through the Power Rail to the power
feed module. The intrinsically safe input
is per DIN EN 50020 safely isolated
from the output and the power supply.
The relay output is in accordance with
IEC 61140 safely isolated from the
power supply.

Function

Output: relay

More products and manuals for Equipment Vega

Models Document Type

VEGABAR 54 4 … 20 mA_HART
User Manual

 
VEGA VEGABAR 54 4 … 20 mA_HART Manual del usuario,

76 pages


VEGASON 54P…56P Profibus PA
User Manual

 
VEGA VEGASON 54P…56P Profibus PA Manuel d’utilisation,

68 pages


VEGAMET 614
User Manual

 
Инструкция по эксплуатации VEGA VEGAMET 614,

56 pages


VEGACAP 82-98
User Manual

 
Инструкция по эксплуатации VEGA VEGACAP 82-98,

36 pages


VEGAMET 515V
User Manual

 
VEGA VEGAMET 515V Manuale d’uso,

64 pages


VEGASON 51K…53K
User Manual

 
VEGA VEGASON 51K…53K Manuel d’utilisation,

48 pages


VEGABAR 41 Profibus PA
User Manual

 
VEGA VEGABAR 41 Profibus PA Manuale d’uso,

36 pages


VEGATRENN 548 V Ex
User Manual

 
VEGA VEGATRENN 548 V Ex User Manual,

16 pages


VEGABAR 74 4 … 20 mA_HART
User Manual

 
VEGA VEGABAR 74 4 … 20 mA_HART Manuale d’uso,

44 pages


VEGABAR 61 4 … 20 mA_HART
User Manual

 
VEGA VEGABAR 61 4 … 20 mA_HART Manuale d’uso,

80 pages


VEGADIF 34 … 51
User Manual

 
VEGA VEGADIF 34 … 51 Manuel d’utilisation,

64 pages


VEGAMET 614
User Manual

 
VEGA VEGAMET 614 Manuale d’uso,

56 pages


D77 Hydrostatic pressure transmitters
User Manual

 
VEGA D77 Hydrostatic pressure transmitters Manuel d’utilisation,

24 pages


VEGAMET 513
User Manual

 
VEGA VEGAMET 513 Manuel d’utilisation,

52 pages


D95 Profibus PA
User Manual

 
VEGA D95 Profibus PA User Manual,

36 pages


VEGABAR 61 4 … 20 mA_HART
User Manual

 
Инструкция по эксплуатации VEGA VEGABAR 61 4 … 20 mA_HART,

84 pages


VEGATRENN 149A Ex
User Manual

 
VEGA VEGATRENN 149A Ex Manuale d’uso,

24 pages


VEGAVIB 63 Lock fitting ARV-VB63.B – pressure range
User Manual

 
VEGA VEGAVIB 63 Lock fitting ARV-VB63.B – pressure range: -1…25 bar User Manual,

16 pages


VEGADIS 50 Ex
User Manual

 
VEGA VEGADIS 50 Ex Benutzerhandbuch,

8 pages


VEGAFLEX 52K
User Manual

 
Инструкция по эксплуатации VEGA VEGAFLEX 52K,

36 pages

VEGA KFA6-SR2-Ex1.W User Manual

Isolated switch amplifiers

KFA6-SR2-Ex1.W

Output: relay

230 V AC

1-channel

Control circuit EEx ia IIC

Reversible mode of operation

1 relay output with 1 changeover contact

EMC acc. to NAMUR NE 21

LB/SC monitoring

Usable up to SIL 2 acc. to IEC 61508

Function

The transformer isolated barrier transfers digital signals from the hazardous area. Sensors per DIN EN 60947-5-6 (NAMUR) and

mechanical contacts may be used as alarms. Control circuits are monitored for lead breakage (LB) and short circuit (SC). The external faults are indicated according to NAMUR NE44 by a red flashing LED. For type KFD2-SR2- Ex1.W, an LB/SC collective error message is in addition transferred through the Power Rail to the power feed module. The intrinsically safe input is per DIN EN 50020 safely isolated from the output and the power supply. The relay output is in accordance with IEC 61140 safely isolated from the power supply.

Input I EEx ia IIC

1+

3-

400 Ω ≤ R ≤ 2 kΩ

1+

10 kΩ

3-

without SC

10 kΩ

2+

3-

without LB, SC 1+

3-

1+

2+

3-

LB

SC

I

II

S3

S1

red

&

yellow

7 8 9

Output

Composition

Subject to reasonable modifications due to technical advances.

Switch S3 in position I

area

Switch S3 in position I

Hazardous

Switch S3 in position I

Switch S3 in position II

+

Safearea

green

+ —

14

15

Power

Power

LB/SC

supply

Rail

collective

only

error message

KFD2-SR2-Ex1.W

103374_ENG.xml 2003-03-25

Copyright Pepperl+Fuchs, Printed in Germany

1

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

Loading…

You can only view or download manuals with

Sign Up and get 5 for free

Upload your files to the site. You get 1 for each file you add

Get 1 for every time someone downloads your manual

Buy as many  as you need

Switch Amplifier

KFA6-SR2-Ex1.W

Assembly

Features • • • • • • •

1-channel isolated barrier 230 V AC supply Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL 2 acc. to IEC 61508/IEC 61511

Front view Removable terminal blue 1 2 4 5

LED yellow: Relay output

3 6

LED green: Power supply

KFA6-SR2-Ex1.W

Function

OUT CHK PWR

This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.

LED red: LB/SC

Switch S1 (mode of operation)

S1 S2 S3 I

The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The barrier output changes state when the input signal changes state. The normal output state can be reversed using switch S1. Switch S3 is used to enable or disable line fault detection of the field circuit.

II

Switch S2 (no functions)

7 8 9 10 11 12 13 14 15

Switch S3 (LB/SC-monitoring) Removable terminals green

During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.

2

Release date 2019-01-24 13:57

Date of issue 2019-01-24

103374_eng.xml

Connection KFA6-SR2-Ex1.W 7 8 9

1+ 2+

10 kΩ 10 kΩ

3400 Ω ≤ R ≤ 2 kΩ

14 15

230 V AC

Zone 0, 1, 2 Div. 1, 2 Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]

Singapore: +65 6779 9091 [email protected]

1

Technical data

KFA6-SR2-Ex1.W

General specifications Signal type

Digital Input

Functional safety related parameters Safety Integrity Level (SIL)

SIL 2

Supply Connection Rated voltage Power dissipation

terminals 14, 15 Ur

Power consumption

207 … 253 V AC, 45 … 65 Hz 1W ≤1W

Input Connection side

field side

Connection

terminals 1+, 2+, 3-

Rated values

acc. to EN 60947-5-6 (NAMUR)

Open circuit voltage/short-circuit current

approx. 8 V DC / approx. 8 mA

Switching point/switching hysteresis

1.2 … 2.1 mA / approx. 0.2 mA

Line fault detection

breakage I ≤ 0.1 mA , short-circuit I > 6 mA

Pulse/Pause ratio

≥ 20 ms / ≥ 20 ms

Output Connection side

control side

Connection

terminals 7, 8, 9

Output

signal ; relay

Contact loading

253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load

Energized/De-energized delay

approx. 20 ms / approx. 20 ms 107 switching cycles

Mechanical life Transfer characteristics Switching frequency

< 10 Hz

Galvanic isolation Input/Output

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Input/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings Display elements

LEDs

Labeling

space for labeling at the front

Directive conformity Electromagnetic compatibility Directive 2014/30/EU

EN 61326-1:2013 (industrial locations)

Low voltage Directive 2014/35/EU

EN 61010-1:2010

Conformity Electromagnetic compatibility

NE 21:2006

Degree of protection

IEC 60529:2001

Input

EN 60947-5-6:2000

Ambient conditions Ambient temperature

-20 … 60 °C (-4 … 140 °F)

Release date 2019-01-24 13:57

Date of issue 2019-01-24

103374_eng.xml

Mechanical specifications Degree of protection

IP20

Connection

screw terminals

Mass

approx. 150 g

Dimensions

20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas EU-Type Examination Certificate

PTB 00 ATEX 2081

Marking

¬ II (1)G [Ex ia Ga] IIC ¬ II (1)D [Ex ia Da] IIIC ¬ I (M1) [Ex ia Ma] I

Input Voltage Current Power Supply Maximum safe voltage Output

Ex ia Uo

10.6 V

Io

19.1 mA

Po

51 mW (linear characteristic)

Um

253 V AC (Attention! Um is no rated voltage.)

Contact loading Maximum safe voltage

253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load Um

253 V AC (Attention! The rated voltage can be lower.)

Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]

Singapore: +65 6779 9091 [email protected]

2

Technical data

KFA6-SR2-Ex1.W

Galvanic isolation Input/Output

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Input/power supply

safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Directive conformity Directive 2014/34/EU

EN 60079-0:2012+A11:2013 , EN 60079-11:2012

International approvals FM approval Control drawing

116-0035

UL approval Control drawing

116-0145

CSA approval Control drawing IECEx approval Approved for

116-0047 IECEx PTB 11.0031 [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

General information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Release date 2019-01-24 13:57

Date of issue 2019-01-24

103374_eng.xml

Supplementary information

Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]

Singapore: +65 6779 9091 [email protected]

3

Technical data

KFA6-SR2-Ex1.W

Configuration Switch position S 1

1 4

2 5

Function Mode of operation Output I (relay) energized

2

3 6

3

Position

with high input current

I

with low input current

II

no function Line fault detection

1

ON

I

OFF

II

OUT CHK PWR

3

9 12 15

Operating status

2

3

8 11 14

1

2

7 10 13

S1 S2 S3

1

S1 S2 S3

I

II

Control circuit

Input signal

Initiator high impedance/ contact opened

low input current

Initiator low impedance/ contact closed

high input current

Lead breakage, lead short-circuit

Line fault

Release date 2019-01-24 13:57

Date of issue 2019-01-24

103374_eng.xml

Factory settings: switch 1, 2 and 3 in position I

Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]

Singapore: +65 6779 9091 [email protected]

4

Technical data

KFA6-SR2-Ex1.W

Maximum switching power of output contacts Resistive load DC

Resistive load AC

I (A) 4

Electrical life max. 105 switching cycles

2 1

Electrical life max. 2.5 x 105 switching cycles

0.5

0.2

20

40

100 200 115 250

U (V)

Release date 2019-01-24 13:57

Date of issue 2019-01-24

103374_eng.xml

The maximum number of switching cycles is depending on the electrical load and may be higher when reduced currents and voltages are applied.

Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]

Singapore: +65 6779 9091 [email protected]

5

Артикул

103374

Производитель

PEPPERL+FUCHS

PEPPERL+FUCHS

Код для заказа

72963

Цена розничная



23473.00 ₽

Цена оптовая

19862.00 ₽

Наличие

1 шт.

Удалённый склад:

901 шт.

Внимание! Актуальные цены будут указаны в выставленном счете или КП.

Условия доставки

Доставка заказа от 250 рублей*

*Весом до 1 кг, до пункта выдачи курьерской службы в г. Москва

  • Доставка по всей России до двери или в пункт выдачи
  • Ежедневная отправка заказов курьерскими службами
  • Бесплатная доставка до терминалов ТК два раза в неделю
  • Самовывоза нет

Понравилась статья? Поделить с друзьями:
  • Kfd2 sr2 ex1 w lb инструкция
  • Kezy ампулы для волос применению инструкция по применению
  • Kezy perma химическая завивка инструкция
  • Kezy one curl инструкция химическая завивка
  • Kezy one curl инструкция на русском языке