General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 207 … 253 V AC, 45 … 65 Hz | |
Power dissipation | 1 W | |
Power consumption | max. 1 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Output | signal ; relay | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 10 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Input | EN 60947-5-6:2000 | |
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 00 ATEX 2081 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Input | Ex ia | |
Voltage | 10.6 V | |
Current | 19.1 mA | |
Power | 51 mW (linear characteristic) | |
Supply | ||
Maximum safe voltage | 253 V AC (Attention! Um is no rated voltage.) | |
Output | ||
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
UL approval | ||
Control drawing | 116-0145 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | ||
IECEx certificate | IECEx PTB 11.0031 | |
IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 13.0 | 27210121 |
ECLASS 12.0 | 27210121 |
ECLASS 11.0 | 27210121 |
ECLASS 10.0.1 | 27210121 |
ECLASS 9.0 | 27210121 |
ECLASS 8.0 | 27210121 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
Details:
KFA6-SR2-Ex1.W
Function
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The barrier output changes state when the input signal changes state. The normal output state can be reversed using switch S1. Switch S3 is used to enable or disable line fault detection of the field circuit.
During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.
Associated Products:
KFA6-SR2-Ex1.W
Matching System Components | ||||
---|---|---|---|---|
|
||||
Accessories | ||||
|
||||
|
||||
|
||||
|
Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.
1
103
37
4_
EN
G.xm
l
2
003
-03-
2
5
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KFA6-SR2-Ex1.W
Isolated switch amplifiers
yellow
green
Output
Power
supply
Saf
e area
Input I EEx ia IIC
Switch S3 in position I
Switch S3 in position I
Switch S3 in position I
Switch S3 in position II
Hazar
dous area
LB
SC
red
Power
Rail
LB/SC
collective
error message
only
KFD2-SR2-Ex1.W
without LB, SC
without SC
&
3-
1+
7
8
9
S1
14 15
+
+
—
2+
II
I
1+
3-
1+
3-
3-
2+
3-
1+
10 k
Ω
10 k
Ω
400
Ω ≤ R ≤ 2 kΩ
S3
—
Composition
230 V AC
• 1-channel
• Control circuit EEx ia IIC
• Reversible mode of operation
• 1 relay output with 1 changeover
contact
• EMC acc. to NAMUR NE 21
• LB/SC monitoring
• Usable up to SIL 2 acc. to IEC 61508
The transformer isolated barrier
transfers digital signals from the
hazardous area. Sensors per
DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as
alarms. Control circuits are monitored
for lead breakage (LB) and short circuit
(SC). The external faults are indicated
according to NAMUR NE44 by a red
flashing LED. For type KFD2-SR2-
Ex1.W, an LB/SC collective error
message is in addition transferred
through the Power Rail to the power
feed module. The intrinsically safe input
is per DIN EN 50020 safely isolated
from the output and the power supply.
The relay output is in accordance with
IEC 61140 safely isolated from the
power supply.
Function
Output: relay
More products and manuals for Equipment Vega
Models | Document Type |
---|---|
VEGABAR 54 4 … 20 mA_HART |
User Manual
76 pages |
VEGASON 54P…56P Profibus PA |
User Manual
68 pages |
VEGAMET 614 |
User Manual
56 pages |
VEGACAP 82-98 |
User Manual
36 pages |
VEGAMET 515V |
User Manual
64 pages |
VEGASON 51K…53K |
User Manual
48 pages |
VEGABAR 41 Profibus PA |
User Manual
36 pages |
VEGATRENN 548 V Ex |
User Manual
16 pages |
VEGABAR 74 4 … 20 mA_HART |
User Manual
44 pages |
VEGABAR 61 4 … 20 mA_HART |
User Manual
80 pages |
VEGADIF 34 … 51 |
User Manual
64 pages |
VEGAMET 614 |
User Manual
56 pages |
D77 Hydrostatic pressure transmitters |
User Manual
24 pages |
VEGAMET 513 |
User Manual
52 pages |
D95 Profibus PA |
User Manual
36 pages |
VEGABAR 61 4 … 20 mA_HART |
User Manual
84 pages |
VEGATRENN 149A Ex |
User Manual
24 pages |
VEGAVIB 63 Lock fitting ARV-VB63.B – pressure range |
User Manual
16 pages |
VEGADIS 50 Ex |
User Manual
8 pages |
VEGAFLEX 52K |
User Manual
36 pages |
Isolated switch amplifiers |
KFA6-SR2-Ex1.W |
Output: relay |
|
230 V AC
•1-channel
•Control circuit EEx ia IIC
•Reversible mode of operation
•1 relay output with 1 changeover contact
•EMC acc. to NAMUR NE 21
•LB/SC monitoring
•Usable up to SIL 2 acc. to IEC 61508
Function
The transformer isolated barrier transfers digital signals from the hazardous area. Sensors per DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as alarms. Control circuits are monitored for lead breakage (LB) and short circuit (SC). The external faults are indicated according to NAMUR NE44 by a red flashing LED. For type KFD2-SR2- Ex1.W, an LB/SC collective error message is in addition transferred through the Power Rail to the power feed module. The intrinsically safe input is per DIN EN 50020 safely isolated from the output and the power supply. The relay output is in accordance with IEC 61140 safely isolated from the power supply.
Input I EEx ia IIC
1+ |
3- |
400 Ω ≤ R ≤ 2 kΩ |
|
1+ |
10 kΩ |
3- |
without SC |
10 kΩ |
||
2+ |
3- |
||
without LB, SC 1+ |
3- |
||
1+ |
2+ |
3- |
|
LB |
|||
SC |
|||
I |
II |
S3 |
|
S1 |
red |
&
yellow
7 8 9
Output
Composition
Subject to reasonable modifications due to technical advances.
Switch S3 in position I
area |
||
Switch S3 in position I |
||
Hazardous |
||
Switch S3 in position I |
||
Switch S3 in position II
+ |
— |
Safearea |
|
green |
|||
+ — |
|||
14 |
15 |
||
Power |
Power |
LB/SC |
|
supply |
Rail |
collective |
|
only |
error message |
||
KFD2-SR2-Ex1.W |
103374_ENG.xml 2003-03-25
Copyright Pepperl+Fuchs, Printed in Germany
1 |
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com |
Loading…
You can only view or download manuals with
Sign Up and get 5 for free
Upload your files to the site. You get 1 for each file you add
Get 1 for every time someone downloads your manual
Buy as many as you need
Switch Amplifier
KFA6-SR2-Ex1.W
Assembly
Features • • • • • • •
1-channel isolated barrier 230 V AC supply Dry contact or NAMUR inputs Relay contact output Line fault detection (LFD) Reversible mode of operation Up to SIL 2 acc. to IEC 61508/IEC 61511
Front view Removable terminal blue 1 2 4 5
LED yellow: Relay output
3 6
LED green: Power supply
KFA6-SR2-Ex1.W
Function
OUT CHK PWR
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
LED red: LB/SC
Switch S1 (mode of operation)
S1 S2 S3 I
The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The barrier output changes state when the input signal changes state. The normal output state can be reversed using switch S1. Switch S3 is used to enable or disable line fault detection of the field circuit.
II
Switch S2 (no functions)
7 8 9 10 11 12 13 14 15
Switch S3 (LB/SC-monitoring) Removable terminals green
During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44.
2
Release date 2019-01-24 13:57
Date of issue 2019-01-24
103374_eng.xml
Connection KFA6-SR2-Ex1.W 7 8 9
1+ 2+
10 kΩ 10 kΩ
3400 Ω ≤ R ≤ 2 kΩ
14 15
230 V AC
Zone 0, 1, 2 Div. 1, 2 Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]
Singapore: +65 6779 9091 [email protected]
1
Technical data
KFA6-SR2-Ex1.W
General specifications Signal type
Digital Input
Functional safety related parameters Safety Integrity Level (SIL)
SIL 2
Supply Connection Rated voltage Power dissipation
terminals 14, 15 Ur
Power consumption
207 … 253 V AC, 45 … 65 Hz 1W ≤1W
Input Connection side
field side
Connection
terminals 1+, 2+, 3-
Rated values
acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current
approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis
1.2 … 2.1 mA / approx. 0.2 mA
Line fault detection
breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio
≥ 20 ms / ≥ 20 ms
Output Connection side
control side
Connection
terminals 7, 8, 9
Output
signal ; relay
Contact loading
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay
approx. 20 ms / approx. 20 ms 107 switching cycles
Mechanical life Transfer characteristics Switching frequency
< 10 Hz
Galvanic isolation Input/Output
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings Display elements
LEDs
Labeling
space for labeling at the front
Directive conformity Electromagnetic compatibility Directive 2014/30/EU
EN 61326-1:2013 (industrial locations)
Low voltage Directive 2014/35/EU
EN 61010-1:2010
Conformity Electromagnetic compatibility
NE 21:2006
Degree of protection
IEC 60529:2001
Input
EN 60947-5-6:2000
Ambient conditions Ambient temperature
-20 … 60 °C (-4 … 140 °F)
Release date 2019-01-24 13:57
Date of issue 2019-01-24
103374_eng.xml
Mechanical specifications Degree of protection
IP20
Connection
screw terminals
Mass
approx. 150 g
Dimensions
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas EU-Type Examination Certificate
PTB 00 ATEX 2081
Marking
¬ II (1)G [Ex ia Ga] IIC ¬ II (1)D [Ex ia Da] IIIC ¬ I (M1) [Ex ia Ma] I
Input Voltage Current Power Supply Maximum safe voltage Output
Ex ia Uo
10.6 V
Io
19.1 mA
Po
51 mW (linear characteristic)
Um
253 V AC (Attention! Um is no rated voltage.)
Contact loading Maximum safe voltage
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load Um
253 V AC (Attention! The rated voltage can be lower.)
Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]
Singapore: +65 6779 9091 [email protected]
2
Technical data
KFA6-SR2-Ex1.W
Galvanic isolation Input/Output
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity Directive 2014/34/EU
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals FM approval Control drawing
116-0035
UL approval Control drawing
116-0145
CSA approval Control drawing IECEx approval Approved for
116-0047 IECEx PTB 11.0031 [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Release date 2019-01-24 13:57
Date of issue 2019-01-24
103374_eng.xml
Supplementary information
Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]
Singapore: +65 6779 9091 [email protected]
3
Technical data
KFA6-SR2-Ex1.W
Configuration Switch position S 1
1 4
2 5
Function Mode of operation Output I (relay) energized
2
3 6
3
Position
with high input current
I
with low input current
II
no function Line fault detection
1
ON
I
OFF
II
OUT CHK PWR
3
9 12 15
Operating status
2
3
8 11 14
1
2
7 10 13
S1 S2 S3
1
S1 S2 S3
I
II
Control circuit
Input signal
Initiator high impedance/ contact opened
low input current
Initiator low impedance/ contact closed
high input current
Lead breakage, lead short-circuit
Line fault
Release date 2019-01-24 13:57
Date of issue 2019-01-24
103374_eng.xml
Factory settings: switch 1, 2 and 3 in position I
Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]
Singapore: +65 6779 9091 [email protected]
4
Technical data
KFA6-SR2-Ex1.W
Maximum switching power of output contacts Resistive load DC
Resistive load AC
I (A) 4
Electrical life max. 105 switching cycles
2 1
Electrical life max. 2.5 x 105 switching cycles
0.5
0.2
20
40
100 200 115 250
U (V)
Release date 2019-01-24 13:57
Date of issue 2019-01-24
103374_eng.xml
The maximum number of switching cycles is depending on the electrical load and may be higher when reduced currents and voltages are applied.
Refer to «General Notes Relating to Pepperl+Fuchs Product Information». Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 www.pepperl-fuchs.com [email protected] [email protected]
Singapore: +65 6779 9091 [email protected]
5
Артикул
103374
Производитель
PEPPERL+FUCHS
PEPPERL+FUCHS
Код для заказа
72963
Цена розничная
23473.00 ₽
Цена оптовая
19862.00 ₽
Наличие
1 шт.
Удалённый склад:
901 шт.
Внимание! Актуальные цены будут указаны в выставленном счете или КП.
Условия доставки
Доставка заказа от 250 рублей*
*Весом до 1 кг, до пункта выдачи курьерской службы в г. Москва
- Доставка по всей России до двери или в пункт выдачи
- Ежедневная отправка заказов курьерскими службами
- Бесплатная доставка до терминалов ТК два раза в неделю
- Самовывоза нет