Isolated switch amplifiers |
KFD2-SR2-Ex2.W |
Output: relay |
|
24 V DC
•2-channel
•Control circuit EEx ia IIC
•Reversible mode of operation
•1 signal output with 1 changeover contact per channel
•EMC acc. to NAMUR NE 21
•LB/SC monitoring
•LB/SC collective error message via Power Rail
•Usable up to SIL 2 acc. to IEC 61508
Function
The transformer isolated barrier transfers digital signals from the hazardous area. Sensors per DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as alarms. Control circuits are monitored for lead breakage (LB) and short circuit (SC). The external faults are indicated according to NAMUR NE44 by a red flashing LED. For type KFD2-SR2- Ex2.W, an LB/SC collective error message is in addition transferred through the Power Rail to the power feed module. The intrinsically safe inputs per DIN EN 50020 are safely isolated from the output and the power supply. Relay outputs are galvanically separated from the mains power in accordance with IEC 61140. Relay outputs are galvanically separated from each other in accordance with
IEC 61140.
Input I EEx ia IIC |
Input II EEx ia IIC |
||||||
1+ |
3- |
4+ |
6- |
||||
400 Ω ≤ R ≤ 2 kΩ |
400 Ω ≤ R ≤ 2 kΩ |
||||||
10 kΩ |
3- |
4+ |
10 kΩ |
6- |
|||
1+ |
|||||||
without SC |
10 kΩ |
5+ |
10 kΩ |
||||
2+ |
3- |
6- |
|||||
without |
|||||||
LB, SC 1+ |
3- |
4+ |
6- |
||||
1+ 2+ |
3- |
4+ 5+ |
6- |
||||
LB |
LB |
||||||
SC |
SC |
||||||
I |
II |
S3 |
I |
II |
S3 |
||
red |
|||||||
S1 |
S2 |
red |
|||||
& |
& |
||||||
green |
|||||||
yellow |
yellow |
||||||
7 |
8 |
9 |
10 11 12 |
||||
Output I |
Output II |
Composition
Subject to reasonable modifications due to technical advances.
Switch S3 in position I
Switch S3 in position I
Switch S3 in position I
zone Hazardouszone0, area,1
Switch S3 in position II
area |
||
+ — |
1 |
Safe |
+—
14 15
Power Power LB/SC supply Rail collective
error message
only KFD2-SR2-Ex2.W
103368_ENG.xml 2003-06-03
Copyright Pepperl+Fuchs, Printed in Germany
1 |
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com |
Loading…
You can only view or download manuals with
Sign Up and get 5 for free
Upload your files to the site. You get 1 for each file you add
Get 1 for every time someone downloads your manual
Buy as many as you need
More products and manuals for Equipment Vega
Models | Document Type |
---|---|
PLICSCOM |
User Manual
44 pages |
VEGABAR 53 Foundation Fieldbus |
User Manual
64 pages |
KFA6-SR2-Ex2.W |
User Manual
3 pages |
VEGAPULS 62 (≥ 2.0.0 — ≥ 4.0.0) standpipe ver. 4 … |
User Manual
60 pages |
B62-30W |
User Manual
20 pages |
PLICSMOBILE T61 |
User Manual
40 pages |
B62-36G |
User Manual
24 pages |
VEGABAR 51 Foundation Fieldbus |
User Manual
76 pages |
VEGAPULS 68 (≥ 2.0.0 — ≥ 4.0.0) 4 … 20 mA_HART — f |
User Manual
84 pages |
POINTRAC 31 8_16 mA_HART — four-wire |
User Manual
56 pages |
B61-300 |
User Manual
20 pages |
VEGABAR 66 4 … 20 mA_HART |
User Manual
80 pages |
VEGAPULS 66 (≥ 2.0.0 — ≥ 4.0.0) standpipe ver. 4 … |
User Manual
64 pages |
VEGAPULS 68 Antenna extension up to 450 °C |
User Manual
16 pages |
Plug connector Harting HAN 7D for continuously mea |
User Manual
8 pages |
VEGABAR 52 Profibus PA — climate compensated |
User Manual
76 pages |
VEGAPULS 61 (≥ 2.0.0 — ≥ 4.0.0) … 20 mA_HART — two |
User Manual
88 pages |
FIBERTRAC 31 4 … 20 mA_HART — four-wire |
User Manual
80 pages |
VEGADIF 65 4 … 20 mA |
User Manual
88 pages |
B53-19 |
User Manual
24 pages |
1
103368_GER.xml 2003-06-03
umutbare Änderungen aufgrund technischer Verbesserungen vorbehalten. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs GmbH • 68301 Mannheim • Telefon +49 621 776-2222 • Telefax +49 621 776 272222 • Internet http://www.pepperl-fuchs.com
KFD2-SR2-Ex2.W
Trennschaltverstärker
Eingang I EEx ia IIC Eingang II EEx ia IIC
grün
rot rot
Ausgang I
Ausgang II
Power
Rail
LB-/LK-
Sammel-
meldung
Schalter S3 in Pos. I
Schalter S3 in Pos. I
Schalter S3 in Pos. I
Schalter S3 in Pos. II
Netz
nur bei
KFD2-SR2-Ex2.W
LB
LK
LB
LK
Nicht-Ex-Bereich
Ex-Bereich, Zone 0, Zone 1
gelb gelb
ohne
LB, LK
ohne LK
1+ 3-
1+ 3-
1+ 3-
2+
3-2+
3-1+
S1 S2
S3 S3
II
I
II
I
1
10 kΩ
10 kΩ
14 15
400 Ω ≤ R ≤ 2 kΩ
4+ 6-
4+ 6-
4+ 6-
5+
6-5+
6-4+
10 kΩ
10 kΩ
400 Ω ≤ R ≤ 2 kΩ
789 101112
+-
+-
&&
Aufbau
24 V DC
• 2-kanalig
• Steuerstromkreis EEx ia IIC
• Umkehrbare Wirkungsrichtung
• 1 Signalausgang mit 1 Wechsler je
Kanal
• EMV gemäß NAMUR NE 21
• LB-/LK-Überwachung
• LB-/LK-Sammelmeldung über Power
Rail
• Bis SIL 2 gemäß IEC 61508
einsetzbar
Der Trennschaltverstärker überträgt di-
gitale Signale aus dem explosionsge-
fährdeten Bereich. Signalgeber können
Sensoren nach DIN EN 60947-5-6
(NAMUR) oder mechanische Kontakte
sein. Die Steuerstromkreise werden auf
Leitungsunterbrechung (LB) und Lei-
tungskurzschluss (LK) überwacht. Die
Anzeige externer Störungen erfolgt ge-
mäß NAMUR NE44 durch eine rot blin-
kende LED. Beim Typ KFD2-SR2-
Ex2.W wird zusätzlich eine LB-/LK-
Sammelmeldung über das Power Rail
auf den Einspeisebaustein übertra-
gen. Die eigensicheren Eingänge sind
gemäß DIN EN 50020 sicher von Aus-
gang und Netz getrennt. Die Relaisaus-
gänge sind gemäß IEC 61140 sicher
vom Netz getrennt. Die Relaisausgän-
ge sind untereinander gemäß
IEC 61140 galvanisch getrennt.
Funktion
Ausgang: Relais
Instruction Manual
1. Marking
Switch amplifier
KFD2-SR2-Ex1.W, KFD2-SR2-Ex1.W.LB, KFD2-SR2-Ex2.W
ATEX certificate: PTB 00 ATEX 2080
ATEX marking:
1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
ATEX certificate: TÜV 99 ATEX 1493 X
ATEX marking: : 1 II 3G Ex ec nC IIC T4 Gc
IECEx certificate: IECEx PTB 11.0034 , IECEx TUN 19.0013X
IECEx marking:
[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
North America Certifcates: E106378 (UL)
Class I, Division 2, Groups A-D, T4
Class I, Zone 2, Group IIC T4
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups A-D; Class II, Division 1, Groups E-G;
Class III
[AEx ia Ga] IIC, [AEx ia Da] IIIC, [Ex ia Ga] IIC, [Ex ia Da] IIIC
USA certificates: FM19US0207X
Class I, Division 2, Groups A-D, T4
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups A-D; Class II, Division 1, Groups E-G;
Class III
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
2. Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation,
maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry
out mounting, installation, commissioning, operation, maintenance, and
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.
3. Reference to Further Documentation
Observe laws, standards, and directives applicable to the intended use
and the operating location.
For mining applications, observe laws, standards, and directives
applicable to the operating location.
The corresponding datasheets, manuals, declarations of conformity, EU-
type examination certificates, certificates, and control drawings if
applicable supplement this document. You can find this information under
www.pepperl-fuchs.com.
If you use the device in safety-related applications, observe the
requirements for functional safety. You can find these requirements in the
functional safety documentation under www.pepperl-fuchs.com.
4. Intended Use
The device is only approved for appropriate and intended use. Ignoring
these instructions will void any warranty and absolve the manufacturer
from any liability.
The device is used in control and instrumentation technology
(C&I technology) for the galvanic isolation of signals such as 20 mA and
10 V standard signals or alternatively for adapting or standardizing signals.
The device has intrinsically safe circuits that are used for operating
intrinsically safe field devices in hazardous areas.
The device transfers digital signals from NAMUR sensors or dry contacts
from the hazardous area to the non-hazardous area.
Use the device only within the specified ambient and operating conditions.
Only use the device stationary.
The device is an associated apparatus according to IEC/EN 60079-11.
The device may be installed in the non-hazardous area.
The device is an electrical apparatus for hazardous areas of Zone 2.
If you use the device in safety-related applications, observe the
information for safety function and safe state.
5. Improper Use
Protection of the personnel and the plant is not ensured if the device is not
used according to its intended use.
6. Mounting and Installation
Do not mount a damaged or polluted device.
The device is designed for mounting on a 35 mm DIN mounting rail
according to EN 60715.
Mount the device in a way that the device is protected against mechanical
hazard. Mount the device in a surrounding enclosure for example.
The device fulfills a degree of protection IP20 according to IEC/EN 60529.
The device must be installed and operated only in a controlled
environment that ensures a pollution degree 2 (or better) according to
IEC/EN 60664-1.
If used in areas with higher pollution degree, the device needs to be
protected accordingly.
Do not mount the device in the dust hazardous area.
The device must be installed and operated only in an environment of
overvoltage category II (or better) according to IEC/EN 60664-1.
Supply the device with a power supply that meets the requirements for
safety extra-low voltage (SELV) or protective extra-low voltage (PELV).
If you are using the Power Rail, supply the Power Rail only via the
corresponding power feed modules or power supplies. Do not supply the
Power Rail via isolators.
Observe the installation instructions according to IEC/EN 60079-14.
If you install the device in safety-related applications, observe the
requirements for functional safety.
Requirements for Cables and Connection Lines
Observe the permissible core cross section of the conductor.
When using stranded conductors, crimp wire end ferrules on the
conductor ends.
Use only one conductor per terminal.
When installing the conductors the insulation must reach up to the
terminal.
Use conductors with a rated temperature suitable for the application.
If you use the device in an ambient temperature above 60 °C, use
conductors rated for a temperature of at least 80 °C.
Observe the tightening torque of the terminal screws.
Requirements for Usage as Associated Apparatus
If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.
Keep the separation distances between all non-intrinsically safe circuits
and intrinsically safe circuits according to IEC/EN 60079-14.
Observe the compliance of the separation distances between two
adjacent intrinsically safe circuits according to IEC/EN 60079-14.
Observe the respective peak values of the field device and the associated
apparatus with regard to explosion protection when connecting intrinsically
safe field devices with intrinsically safe circuits of associated apparatus
(verification of intrinsic safety). Also observe IEC/EN 60079-14 and
IEC/EN 60079-25.
Requirements for Equipment Protection Level Gc
The device must be installed and operated only in surrounding enclosures
that
l
comply with the requirements for surrounding enclosures according to
IEC/EN 60079-0,
l
are rated with the degree of protection IP54 according to
IEC/EN 60529.
Ensure that the surrounding enclosure can only be opened with a tool.
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
7. Operation, Maintenance, Repair
If you operate the device in safety-related applications, observe the
requirements for functional safety. For the proof test, plan appropriate
intervals for the operation in low demand mode.
Do not use a damaged or polluted device.
Do not repair, modify, or manipulate the device.
If there is a defect, always replace the device with an original device.
Requirements for Equipment Protection Level Gc
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Only use operating elements in the absence of a potentially explosive
atmosphere.
8. Delivery, Transport, Disposal
Check the packaging and contents for damage.
Check if you have received every item and if the items received are the
ones you ordered.
DOCT-6724 / 2020-03 1 / 2
1
103
36
8_
EN
G.xm
l
2
003
-06-
0
3
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KFD2-SR2-Ex2.W
Isolated switch amplifiers
Input I EEx ia IIC
Input II EEx ia IIC
green
red
red
Output
I
Output
II
Power
Rail
LB/SC
collective
error message
Switch S3 in position I
Switch S3 in position I
Switch S3 in position I
Switch S3 in position II
Power
supply
only
KFD2-SR2-Ex2.W
LB
SC
LB
SC
Saf
e area
Hazar
dous area,
zone 0,
zone 1
yellow
yellow
without
LB, SC
without SC
1+
3-
1+
3-
1+
3-
2+
3-
2+
3-
1+
S1
S2
S3
S3
II
I
II
I
1
10 k
Ω
10 k
Ω
14 15
400
Ω ≤ R ≤ 2 kΩ
4+
6-
4+
6-
4+
6-
5+
6-
5+
6-
4+
10 k
Ω
10 k
Ω
400
Ω ≤ R ≤ 2 kΩ
7
8
9
10 11 12
+
—
+
—
&
&
Composition
24 V DC
• 2-channel
• Control circuit EEx ia IIC
• Reversible mode of operation
• 1 signal output with 1 changeover
contact per channel
• EMC acc. to NAMUR NE 21
• LB/SC monitoring
• LB/SC collective error message via
Power Rail
• Usable up to SIL 2 acc. to IEC 61508
The transformer isolated barrier
transfers digital signals from the
hazardous area. Sensors per
DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as
alarms. Control circuits are monitored
for lead breakage (LB) and short circuit
(SC). The external faults are indicated
according to NAMUR NE44 by a red
flashing LED. For type KFD2-SR2-
Ex2.W, an LB/SC collective error
message is in addition transferred
through the Power Rail to the power
feed module. The intrinsically safe
inputs per DIN EN 50020 are safely
isolated from the output and the power
supply. Relay outputs are galvanically
separated from the mains power in
accordance with IEC 61140. Relay
outputs are galvanically separated from
each other in accordance with
IEC 61140.
Function
Output: relay
Артикул: 203355
Барьер искрозащиты для сигналов DI. 2 канала
Производитель:
PEPPERL+FUCHS
Производитель: PEPPERL+FUCHS
Технические данные PDF
Краткое описание: технические характеристики KFD2-SR2-EX2.W
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
SIL Claim Level | SIL 2 , see functional safety manual | |
Performance level (PL) | PL d , see functional safety manual | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 … 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 50 mA | |
Power dissipation | ≤ 1 W | |
Power consumption | ≤ 1 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 | |
Output I, II | signal, relay | |
Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | ≤ 10 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 | |
Degree of protection | IEC 60529:1989+A1:1999+A2:2013 | |
Functional safety | IEC/EN 61508:2010 | |
Input | EN 60947-5-6:2000 | |
Ambient conditions | ||
Ambient temperature | -20 … 70 °C (-4 … 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 00 ATEX 2080 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Input | Ex ia | |
Voltage | 10.5 V | |
Current | 13 mA | |
Power | 34 mW (linear characteristic) | |
Supply | ||
Maximum safe voltage | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) | |
Output | ||
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | II (3)G [Ex ic Gc] IIC | |
Input | Ex ic | |
Voltage | 10.5 V | |
Current | 13 mA | |
Power | 34 mW (linear characteristic) | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | II 3G Ex ec nC IIC T4 Gc | |
Output | ||
Contact loading | 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 | |
International approvals | ||
FM approval | ||
FM certificate | FM19US0207X | |
Control drawing | 116-0035 | |
UL approval | E106378 | |
Control drawing | 116-0473 (cULus) | |
Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load | |
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
IECEx approval | ||
IECEx certificate | IECEx PTB 11.0034 , IECEx TUN 19.0013X | |
IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |