Plena voice alarm controller инструкция

  • Categories
  • Brands
  • Home

  • Bosch

  • Musical Equipment

  • Plena Voice Alarm System

Owner’s manuals and user’s guides for Musical Equipment Bosch Plena Voice Alarm System.
We providing 3 pdf manuals Bosch Plena Voice Alarm System for download free by document types: User Manual, Service Manual

Table of contents

Table of contents

Table of contents

[Page 1] Bosch Plena Voice Alarm System

Plena Voice Alarm System en Installation and Operation manual

[Page 2] Bosch Plena Voice Alarm System

[Page 3] Bosch Plena Voice Alarm System

Table of contents 1 Safety 8 1.1 Important Safeguards 8 1.2 Important Notices 8 2 About this manual 9 2.1 Purpose of this manual 9 2.2 Intended audience 9 2.3 Related documentation 9 2.4 Alerts and notice signs 9 2.5 Conversion tables 10 2.6 Nomencla…

[Page 4] Bosch Plena Voice Alarm System

3.12.4 Hotel 40 3.13 Calls and priorities 42 3.13.1 Priority 42 3.13.2 Mergeable messages 42 3.13.3 Business call 42 3.13.4 Emergency call 42 4 Installation 43 4.1 Voice Alarm Controller 43 4.2 Voice Alarm Router 43 4.3 Call Station Keypad 44 4.4 Voi…

[Page 5] Bosch Plena Voice Alarm System

5.4.4 Power 71 5.5 Voice Alarm Remote Control Kit 71 5.5.1 Rear panel 71 5.5.2 LEDs 71 5.5.3 Lamps 72 5.5.4 Relays 72 5.6 Remote Control Extension 73 5.6.1 Remote control 73 5.6.2 Status output contacts 73 5.6.3 Power 73 5.7 Remote Control Extension …

[Page 6] Bosch Plena Voice Alarm System

6.4.3 Speech filter 84 6.4.4 Termination 84 6.5 Remote control 85 6.5.1 Remote control ID 85 6.5.2 Monitor 85 6.5.3 Termination switch 85 6.6 Remote control extension 86 6.6.1 Remote control extension ID 86 6.6.2 Termination switch 86 7 Operation 87 …

[Page 7] Bosch Plena Voice Alarm System

8.14 A click sounds through the loudspeakers at regular intervals 103 8.15 Password not working 103 8.16 Configuration download fails 103 8.17 Can’t retrieve the original wave files with the configuration download 104 9 Maintenance 105 9.1 Clean th…

[Page 8] Bosch Plena Voice Alarm System

Safety Important Safeguards Prior to installing or operating products, always read the Important Safety Instructions which are available as a separate multilingual document: Important Safety Instructions (Safety_ML). These instructions are supplied t…

[Page 9] Bosch Plena Voice Alarm System

About this manual Purpose of this manual The purpose of the Installation and Operation manual is to provide information that is required to install, configure and operate a Plena Voice Alarm System. Intended audience The Installation and Operation ma…

[Page 10] Bosch Plena Voice Alarm System

Conversion tables In this manual, SI units are used to express lengths, masses, temperatures etc. These can be converted to non-metric units using the information provided below. 1 in = 25.4 mm 1 mm = 0.03937 in 1 in = 2.54 cm 1 cm = 0.3937 in 1 ft =…

[Page 11] Bosch Plena Voice Alarm System

Nomenclature Throughout this manual, terms like “Controller”, “Router” and “Remote Control” are used to describe the various component types, as indicated below. Component description Component type designation Power Amplifier 360/240W LB…

[Page 12] Bosch Plena Voice Alarm System

System overview Voice Alarm System The Plena Voice Alarm System is a public address and voice alarm system in which features for compliance to evacuation standards such as EN60849, NEN2575, BS5839/8 and EN54-16 are integrated. Application types Typic…

[Page 13] Bosch Plena Voice Alarm System

Voice Alarm Controller The Voice Alarm Controller is the heart of the Plena Voice Alarm System. The voice alarm controller distributes emergency calls, business calls as well as background music (BGM) to up to 6 loudspeaker zones. Figure 3.1: Voice A…

[Page 14] Bosch Plena Voice Alarm System

Remote control With the Voice Alarm Remote Control, it is possible to control the voice alarm controller from another site. The remote control is also available as kit (Voice Alarm Remote Control Kit) for creating customized solutions. The maximum nu…

[Page 15] Bosch Plena Voice Alarm System

2. Fault indicators: Twelve yellow system fault LEDs (Processor reset, Network, Call/EMG, Music/Spare, Ground short, Input, Mains, Battery, Message, EMG mic, RCP and Router) and twelve yellow loudspeaker line fault LEDs. Fault indication is only poss…

[Page 16] Bosch Plena Voice Alarm System

15. Microphone socket: A socket to connect the hand-held emergency microphone (see section Emergency microphone, page 49). 16. Bracket: A bracket for the hand-held emergency microphone that is supplied with the voice alarm controller. 17. Monitoring …

[Page 17] Bosch Plena Voice Alarm System

34. Router socket: An RJ45 socket to connect voice alarm routers to the voice alarm controller (see section Voice alarm routers, page 51). 35. Remote control panel socket: Two RJ45 sockets to connect remote control panels (Fireman’s panel, Remote C…

[Page 18] Bosch Plena Voice Alarm System

Voice Alarm Router With the Voice Alarm Router, the number of loudspeaker zones and trigger inputs in the system can be increased. Figure 3.3: Voice alarm router Loudspeaker zones A voice alarm controller can serve and manage 6 loudspeaker zones. To …

[Page 19] Bosch Plena Voice Alarm System

Controls, connectors and indicators Plena Voice Alarm Router 0 dB -6dB -20dB B Processor reset Network Call/EMG Music/Spare Ground short Input Mains Battery Zone1 Zone2 Zone3 Zone4 Zone5 Zone6 Alarm Zone select A Fault Indicators Zone select Zone1 …

[Page 20] Bosch Plena Voice Alarm System

6. External power amplifier 1 (input): An input to connect an external power amplifier (see section External power amplifiers, page 67). These pins are used in combination with the external power amplifier output (no. 18). 7. Call output: An output t…

[Page 21] Bosch Plena Voice Alarm System

Call Station The Call Station can be connected to the Plena Voice Alarm System to make business calls. The maximum number of call stations in a Plena Voice Alarm System is 8. Figure 3.5: Call Station Buttons Each call station has zone select buttons …

[Page 22] Bosch Plena Voice Alarm System

Keypad Each voice alarm router can add 6 extra loudspeaker zones to the system. To be able to distribute calls to the extra zones, it is possible to connect Remote Control Extension to the call station. The maximum number of keypads that can be conne…

[Page 23] Bosch Plena Voice Alarm System

Controls, connectors and indicators Plena ON 1 2 3 4 5 6 7 8 2 3 9 5 1 4 8 6 7 Figure 3.7: Top and bottom views of the call station Controls, indicators and connectors on the call station: 1. Power indicator: A green LED to indicate that the call…

[Page 24] Bosch Plena Voice Alarm System

Call Station Keypad Plena 1 2 2 Figure 3.8: Top and bottom views of the call station keypad Controls, indicators and connectors on the call station keypad: 1. Zone selection buttons: Seven buttons to select the zones to which the business call is…

[Page 25] Bosch Plena Voice Alarm System

Voice Alarm Remote Control 0 dB -6dB -20dB Processor reset Network Call/EMG Music/Spare Ground short Input Mains Battery Zone1 Zone2 Zone3 Zone4 Zone5 Zone6 Alarm Zone select Plena Voice Alarm Remote Control Fault Indicators Zone select Indicator te…

[Page 26] Bosch Plena Voice Alarm System

5. Emergency call zone selectors: Six buttons to select the zones to which the emergency call must be distributed (see section Emergency state, page 91). Each button has a green and a red LED. The six red LEDs indicate the zones that are selected for…

[Page 27] Bosch Plena Voice Alarm System

21. Emergency microphone volume control: A rotary knob to set the volume of the hand-held emergency microphone. 22. Monitoring speaker volume control: A rotary knob to set the volume of the monitoring loudspeaker. 23. Trigger outputs: Three general p…

[Page 28] Bosch Plena Voice Alarm System

Remote Control Extension Plena Remote Control Extension 0 dB -6dB -20dB B Processor reset Network Call/EMG Music/Spare Ground short Input Mains Battery Zone1 Zone2 Zone3 Zone4 Zone5 Zone6 Alarm Zone select A Fault Ind…

[Page 29] Bosch Plena Voice Alarm System

7. Firmware upgrade switch: A switch to upgrade the firmware of the remote control extension. 8. System sockets: One RJ45 socket to connect the remote control extension to the remote control (see section Remote control extensions, page 70). 9. Config…

[Page 30] Bosch Plena Voice Alarm System

Fireman’s Panel Plena Fireman’s Panel EMG mic Fault Indicators Processor reset Network Call/EMG Music/Spare Ground short Input A B A B A B Zone1 Zone2 Zone3 Disable For service only On 1 2 Termination RCP ID Controller Monitoring Speaker Warn…

[Page 31] Bosch Plena Voice Alarm System

7. Fault reset: A push button to reset the fault state (see section Fault State, page 96). 8. Fault indicators: Twelve yellow system fault LEDs (Processor reset, Network, Call/EMG, Music/Spare, Ground short, Input, Mains, Battery, Message, EMG mic, R…

[Page 32] Bosch Plena Voice Alarm System

End Of Line detection board The End Of Line (EOL) detection board makes a continuous check of the integrity of the loudspeaker line based on a pilot tone. This check is in addition to the check given by the impedance measurement. The pilot tone is in…

[Page 33] Bosch Plena Voice Alarm System

and 2 offices, each requiring a single loudspeaker. The canteen, assembly hall, playing fields and corridors typically require more loudspeakers per zone. An additional Plena Power Amplifier is used as a spare amplifier. Layout 2 Z7-12 Z13-18 Z19-24…

[Page 34] Bosch Plena Voice Alarm System

Zone Description Power Z25-26 Offices 2 x 6 W Z27 Corridors 4 x 6 W Z28 Assembly hall 2 x 6 W Z29 Lunch canteen 2 x 6 W Z30 Playing fields 1 x 10 W Total 232 W Table 3.2: Zones 34 en | System overview Plena 2013.07 | V2.0 | Installation and Opera…

[Page 35] Bosch Plena Voice Alarm System

Swimming pool Swimming pools and other indoor sports and recreational facilities are typical examples of smaller applications with few zones. The main priorities are excellent speech intelligibility and compliance with IEC 60849 standard (and its nat…

[Page 36] Bosch Plena Voice Alarm System

Layout 6 1 Z1-5 5 3 2 4 Figure 3.15: Example of a swimming pool Number Unit Description No. 1 LBB 1990/00 Controller 1 x 2 LBB 1996/00 Remote control 1 x 3 LBB 1956/00 Call station 1 x 4 LBB 1957/00 Call station keypad 4 x 5 LBB 1935/20 Power Ampli…

[Page 37] Bosch Plena Voice Alarm System

Shopping mall Shopping malls are typical example of applications with a large number of zones with varying output power requirements per zone. The priorities are speech intelligibility and compliance with IEC 60849 standard (and its national equivale…

[Page 38] Bosch Plena Voice Alarm System

Layout 2 Z49-54 Z43-48 Z37-42 Z31-36 Z25-30 Z19-24 Z13-18 Z7-12 Z1-6 9 8 8 6 3 7 10 1 4 5 Figure 3.16: Example of a shopping mall Number Unit Description No. 1 LBB 1990/00 Controller 1 x 2 LBB 1992/00 Router 8 x 3 LBB 1995/00 Fireman’s Panel 4 …

[Page 39] Bosch Plena Voice Alarm System

Zone Description Power Z37-42 6 medium-sized stores 24 x 6 Z47 Security control room 1 x 6 W Z48 Offices 4 x 6 W Z49 Walkways ground floor 4 x 6 W Z50 Gallery 1st floor 10 x 6 W Z51 Gallery 2nd floor 10 x 6 W Z52 Main public square 4 x 18 W Z53 Parki…

[Page 40] Bosch Plena Voice Alarm System

Hotel Smaller hotels are typical examples of applications with relatively few zones, each with a medium to high output power requirement. The priorities are speech intelligibility and compliance with IEC 60849 standard. In addition to mandatory voice…

[Page 41] Bosch Plena Voice Alarm System

Layout 2 9 1 Z7-12 Z1-6 7 8 5 3 6 4 Figure 3.17: Example of a hotel Number Unit Description No. 1 LBB 1990/00 Controller 1 x 2 LBB 1992/00 Router 1 x 3 LBB 1996/00 Remote control 1 x 4 LBB 1997/00 Remote control extension 1 x 5 LBB 1956/00 Call sta…

[Page 42] Bosch Plena Voice Alarm System

Calls and priorities As the Plena Voice Alarm System is a public address and emergency sound system, it is used to distribute background music, business calls and emergency calls. Priority To each call, a priority is assigned. When two or more calls …

[Page 43] Bosch Plena Voice Alarm System

Installation Voice Alarm Controller The voice alarm controller is suitable for table‑top and 19‑inch rack-mounting installation. Two brackets for rack-mounting are supplied. Figure 4.1: Brackets for rack-mounting Make sure that there is a free sp…

[Page 44] Bosch Plena Voice Alarm System

Call Station Keypad Call station keypads can be connected to call stations or to other call station keypads. 11 22 44 33 55 66 77 1 2 3 Figure 4.2: Connecting call station keypads Voice Alarm Remote Control The remote control is suitable for table�…

[Page 45] Bosch Plena Voice Alarm System

Remote Control Extension The remote control extension is suitable for table‑top and 19‑inch rack mounting installation. Two brackets for rack-mounting are supplied. Installing a remote control extension is similar to installing a voice alarm cont…

[Page 46] Bosch Plena Voice Alarm System

Installation of a single EOL 1. Connect the two cables at the end of the 100 V loudspeaker line to the Input 100 V LS on the EOL board. 2. Connect the two cables from an Emergency Trigger Input on the Voice Alarm Controller to TRGA on the EOL. 3. Con…

[Page 47] Bosch Plena Voice Alarm System

JP1 JP1 JP1 Last EOL board First EOL board 20k Figure 4.5: Trigger input indication 5. In the configuration program, set the Action Programming for the relevant input to Fault and EOL. 6. Enter the Zone or Zone group that is monitored …

[Page 48] Bosch Plena Voice Alarm System

Dummy load To install the Dummy load do as follows: 1. Connect the two leads onto the connection terminals of the last loudspeaker in a line. 2. Attach the Dummy Load circuit board in the loudspeaker cabinet to the mounting studs. Notice! In some lou…

[Page 49] Bosch Plena Voice Alarm System

Connection Voice Alarm Controller Emergency microphone The voice alarm controller has 1 connector for an emergency microphone. A hand-held emergency microphone is supplied with the voice alarm controller. See for installation details below. Turn the …

[Page 50] Bosch Plena Voice Alarm System

Call station The voice alarm controller has 2 sockets for Call Stations. Use CAT‑5 Ethernet cables with RJ45 plugs to connect call stations to the voice alarm controller. When the system requires more than 2 call stations, use the system sockets on…

[Page 51] Bosch Plena Voice Alarm System

Voice alarm routers The voice alarm controller has 1 socket for Voice Alarm Routers. Use shielded CAT‑5 Ethernet cables with RJ45 plugs to connect a voice alarm router to the voice alarm controller. When the system requires more than 1 voice alarm …

[Page 52] Bosch Plena Voice Alarm System

External power amplifier The voice alarm controller has 1 external power amplifier output (line level, 1 V) and 1 external power amplifier input (100 V) to connect an external power amplifier. The function of the external power amplifier (e.g. a Plen…

[Page 53] Bosch Plena Voice Alarm System

Remote controls The voice alarm controller has 2 sockets for remote controls. Use shielded CAT‑5 Ethernet cables with RJ45 plugs to connect a remote control to the voice alarm controller. See the connection details below: Monitoring Speaker Contro…

[Page 54] Bosch Plena Voice Alarm System

Loudspeakers The voice alarm controller has 6 zone outputs (Z1 to Z6). Each zone output consists of 2 redundant loudspeaker lines (line A and line B). Normally, calls and BGM are distributed to a zone over both loudspeaker lines. If one of the loudsp…

[Page 55] Bosch Plena Voice Alarm System

If it is necessary to detect the removal or failure of a single loudspeaker, the following is advised: – Do not connect more than 5 loudspeakers to the same loudspeaker line (line A or line B). Field tests have shown that the impedance of loudspeak…

[Page 56] Bosch Plena Voice Alarm System

Volume overrides The voice alarm controller has 6 override outputs; 1 for each zone in the system. These are suitable for 4‑wire override (24 V) and 3‑wire override. Notice! By default, the voice alarm controller is configured for 4‑wire (24 V)…

[Page 57] Bosch Plena Voice Alarm System

Normally, when there are no active calls, the Z+ pins are internally connected to the NC contact of the Volume Override. At the moment a call is started in a zone, the Z+ pin of the zone is internally connected to the NO contact of the Volume Overrid…

[Page 58] Bosch Plena Voice Alarm System

4. Enable 3‑wire volume override in the configuration software. Notice! See the Configuration Software Manual for more information about the configuration software. ! Caution! Make sure that the correct connections have been made and the system i…

[Page 59] Bosch Plena Voice Alarm System

Mic/line input with VOX The voice alarm controller has 1 mic/line input with voice-activated (VOX) functionality. This input has 2 sockets; a balanced XLR socket and a balanced 6.3 mm jack socket. The signals from both sockets are mixed to form a sin…

[Page 60] Bosch Plena Voice Alarm System

For example, the mic/line input with VOX functionality can be used to create a supervised link to another emergency sound system (e.g. a Praesideo system). BGM inputs The voice alarm controller has 2 BGM inputs. Each BGM input has a double cinch sock…

[Page 61] Bosch Plena Voice Alarm System

Status output contacts The voice alarm controller has 3 status output contacts to indicate the current system state. These are used to send the status of the Plena Voice Alarm Systemto third party equipment or to connect sounders or similar indicatin…

[Page 62] Bosch Plena Voice Alarm System

Power Introduction The voice alarm controller has the following power connections: – Mains power connection. – Back-up power connection. Mains power Proceed as follows to connect the voice alarm controller to the mains power: 4 Select the local m…

[Page 63] Bosch Plena Voice Alarm System

COM NC NO 10k 10k Trigger input/24V D C out Business Emergency NC TRG2 Override/Trigger Output AU X L R PC Digital Message Monitoring Speaker Remote C ontrol Panel Impedance Calibration In Voice AlarmController Max. output power 36 0W Rated output po…

[Page 64] Bosch Plena Voice Alarm System

Trigger inputs Introduction The voice alarm controller has a terminal block to which 6 emergency (EMG) and 6 business trigger inputs can be connected. Third party systems can use the trigger inputs to start emergency and business calls in the Plena V…

[Page 65] Bosch Plena Voice Alarm System

Business trigger inputs The lower part of the terminal block contains the business trigger inputs. The business trigger inputs have a lower priority than the emergency trigger inputs. 1 2 3 4 5 6 VOX Switch 1 2 …

[Page 66] Bosch Plena Voice Alarm System

Voice Alarm Router Voice alarm controller Connect the voice alarm router to the voice alarm controller (see section Voice alarm routers, page 51). Loudspeakers The voice alarm router has 6 zone outputs (Z1 to Z6). The procedure for connecting loudspe…

[Page 67] Bosch Plena Voice Alarm System

External power amplifiers The voice alarm router has 2 external power amplifier outputs (line level, 1 V) and 1 external power amplifier input (100 V) to connect two external power amplifiers. The function of the external power amplifier (e.g. a Plen…

[Page 68] Bosch Plena Voice Alarm System

Design & Quality The Netherlands Out GND Amplifier 1 Amplifier 2 100V 70V 0 0 line in line out 1 2 3 1 2 3 GND GND+ + — — 0V 0 100V 0 100V 70V 0 100V TRG1 TRG2 NC B Failure 0V 0 100V 0 100V 0 +24V- Booster 2 in Z5 Z6 DC In Z1 Z2…

[Page 69] Bosch Plena Voice Alarm System

Call Station Voice alarm controller Connect the call station to the voice alarm controller (see section Call station, page 50). Power supply If the cable between the voice alarm controller or the previous call station is longer than 100 m, the call s…

[Page 70] Bosch Plena Voice Alarm System

Voice Alarm Remote Control Voice alarm controller Connect the remote control panel to the voice alarm controller (see section Remote controls, page 53). Remote control extensions The remote controller has 1 socket for remote control extensions (Remot…

[Page 71] Bosch Plena Voice Alarm System

Power Connect a power supply to the remote control panel: Design & Quality T he Netherlands R C Panel Max . input power 30 0mA , 24V DC S/ N. A 0 35413 N663 Charger 24 VDC — + Figure 5.25: Connecting a 24 VDC power supply Voice Alarm Remote Co…

[Page 72] Bosch Plena Voice Alarm System

Lamps To the LEDS/LAMPS connectors on the front panel of the remote control kit, lamps can be connected: GND max. 52 V LEDS/LAMPS connector < 200 mA Figure 5.27: Connecting lamps Relays To the LEDS/LAMPS connectors on the front panel of the remo…

[Page 73] Bosch Plena Voice Alarm System

Remote Control Extension Remote control Connect the remote control extension to the remote control (see section Remote control extensions, page 70). Status output contacts The remote control extension has 3 status output contacts to indicate the curr…

[Page 74] Bosch Plena Voice Alarm System

Relays To the LEDs/LAMPS connectors on the front panel of the remote control extension kit, relays can be connected (see Voice Alarm Remote Control kit, page 27). Fireman’s Panel Voice alarm controller Connect the fireman’s panel to the voice ala…

[Page 75] Bosch Plena Voice Alarm System

Configuration A number of functions of the Plena Voice Alarm System is hardware configured using, for example, DIP switches and volume controls. Other parts of the system must be software configured using the Plena Voice Alarm System configuration so…

[Page 76] Bosch Plena Voice Alarm System

Monitor If the Monitor switch is in the ON position, the internal monitoring loudspeaker of the voice alarm controller is switched on. The volume of the monitoring loudspeaker is set with the Monitoring Speaker volume control (see Controls, connector…

[Page 77] Bosch Plena Voice Alarm System

1-Channel mode operation If the 2ch operation switch (see 2-Channel mode operation, page 78) is in the OFF position, the system operates in the 1‑channel mode. Voice alarm controller In the 1‑channel mode, all calls and BGM are amplified by the i…

[Page 78] Bosch Plena Voice Alarm System

2-Channel mode operation If the 2ch operation switch (see System settings, page 75) is in the ON position, the system operates in the 2‑channel mode. Voice alarm controller In the 2‑channel mode, the BGM is amplified by the internal power amplifi…

[Page 79] Bosch Plena Voice Alarm System

Notice! See the Configuration Software Manual for more information about the configuration software. Processor reset Watchdog If supervision is enabled (see section Supervision, page 78), the processor of the voice alarm controller is supervised by a…

[Page 80] Bosch Plena Voice Alarm System

Emergency trigger inputs If supervision is enabled and input supervision is switched on (see section Supervision, page 78), the system can supervise the emergency trigger inputs. For each emergency trigger input, supervision can be switched on and of…

[Page 81] Bosch Plena Voice Alarm System

Short-circuit supervision If line supervision is switched on, the voice alarm controller continuously monitors all loudspeaker lines in the system for short-circuits. If a short‑circuit is detected, the line output of the short-circuited line is is…

[Page 82] Bosch Plena Voice Alarm System

Phantom power Vox Speech filter Off On Mic/Line Figure 6.5: VOX volume control VOX If the VOX switch is in the OFF position, the input is activated when the voltage of the signal of the source is above the specified threshold. If the VOX switch is i…

[Page 83] Bosch Plena Voice Alarm System

Call station The call stations are configured using the DIP switch at the bottom: ON 1 2 3 4 5 6 7 8 Figure 6.7: Call station DIP switches DIP switch Description 1, 2, 3, 4 Set the ID of the call station. See section Call station ID, page 83. 5, …

[Page 84] Bosch Plena Voice Alarm System

Speech filter If switch 7 is in the ON position, a speech filter is activated for the call station. The speech filter improves the speech intelligibility by cutting off the lower frequencies. Termination The last call station in a sequence of looped-…

[Page 85] Bosch Plena Voice Alarm System

Remote control The remote controls are configured using a DIP switch: Figure 6.8: Remote control settings Remote control ID The ID of the remote control is set using the Remote Control Panel ID switch. The ID of the remote control must be the same as…

[Page 86] Bosch Plena Voice Alarm System

Remote control extension The remote control extensions are configured using an ID selector and a switch: 6 1…9 ID 1 2 3 4 5 7 9 8 RCP ext. In RCP ext. Out Off On Termination 3 Figure 6.9: Remote control settings Remote control extension ID The ID…

[Page 87] Bosch Plena Voice Alarm System

Operation Switch on Notice! It is assumed that the APR mode switch (see section APR mode, page 76) is in the OFF position. Voice alarm controller Switch on Put the power switch on the rear of the voice alarm controller in the I position. 115V~ 230V~…

[Page 88] Bosch Plena Voice Alarm System

– After the settings of the connected loudspeakers have been changed. Background music The background music (BGM) is controlled using the BGM controls on the front of the voice alarm controller, voice alarm router and their remote control and remot…

[Page 89] Bosch Plena Voice Alarm System

Adjust volume The voice alarm controller has two types of controls to adjust the BGM volume. The overall (maximum) volume of the BGM source is set with the master volume control, which is located below the BGM source selector (Select button, see Sele…

[Page 90] Bosch Plena Voice Alarm System

Notice! See the Configuration Software Manual for more information about the configuration software. Select zones Select the zones to which the business call must be distributed with the zone selection buttons on the call station or its keypads. A gr…

[Page 91] Bosch Plena Voice Alarm System

Indicator Position Description Yellow Left System fault Green Center Talk (green). Busy (Yellow flashing). Red Right System in emergency state, call station disabled Table 7.1: Call station status indicators Emergency state Emergency calls can only b…

[Page 92] Bosch Plena Voice Alarm System

At the moment the emergency state is entered, a beeper starts and the EMG status output contact are closed. See section Exit the emergency state, page 92 for information about exiting the emergency state. Acknowledge the emergency state The beeper ca…

[Page 93] Bosch Plena Voice Alarm System

Select zones Select the zones to which the live speech must be distributed with the Zone select buttons on the front of the voice alarm controller or the remote controls. A red LED indicates the zones to which the live speech is distributed. – If t…

[Page 94] Bosch Plena Voice Alarm System

Make the announcement Push the push‑to‑talk (PTT) button of the emergency microphone to make an announcement. The live speech is only distributed to the selected zones (see section Select zones, page 93). At the moment the PTT button of the emerg…

[Page 95] Bosch Plena Voice Alarm System

Notice! If no additional action is taken within 10 seconds after the last Zone select button has been pushed (for example pushing the Alert message button), the zone selection is cancelled. Zone select Zone1 Zone2 Fault Reset EMG Ack Figure 7.15: Z…

[Page 96] Bosch Plena Voice Alarm System

Distribute the alarm message Distributing the default alarm message is similar to distributing the default alert message (see section Distribute the alert message, page 94). Push the Alarm message button instead of the Alert message button. The alarm…

[Page 97] Bosch Plena Voice Alarm System

Reset the fault state Reset the fault state by pushing the Fault Reset button on the front of the voice alarm controller or the remote controls. The fault state can also be reset by pushing the Fault Reset button on the fireman’s panel. In order to…

[Page 98] Bosch Plena Voice Alarm System

Fault indicators The voice alarm controller, voice alarm router and remote controls have two types of fault indicators: System fault indicators and loudspeaker line fault indicators (see Supervision, page 78). The system fault indicators provide info…

[Page 99] Bosch Plena Voice Alarm System

Indicator Description Recommended action Additional information Processor reset A processor reset is detected. Switch the voice alarm controller off and on again. See section Processor reset, page 79. Network A network fault is detected. Check all ne…

[Page 100] Bosch Plena Voice Alarm System

Indicator Description Recommended action Additional information Message A message fault is detected. Switch the voice alarm controller off and on again. See section Message supervision, page 80. EMG mic An emergency microphone fault is detected. Chec…

Plena Voice Alarm System

en

Basic System Manual

Voice Alarm System

Plena Voice Alarm System | Basic System Manual | Important Safeguards

Important Safeguards

Prior to installing or operating this product, always read the Important Safety Instructions which are available as a separate document (9922 141 7014x). These instructions are supplied together with all equipment that can be connected to the mains.

en | 3

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Important Notices

Important Notices

When using routers, keypads or more than one call station, configure the controller using the supplied software.

Use shielded cable (Cat-5) between the routers and the controller.

The factory default setting of the Plena Voice Alarm

Controller is as follows:

• Stand-alone unit configured for an ISO 60849 compliant system when used with a spare power amplifier from the Plena range and compliant wiring and loudspeakers.

• One channel system.

• Supervision on for:

• Loudspeaker lines

(90 seconds interval, 15% accuracy)

• Main and spare power amplifier

• Short to ground (“Ground short”)

• Mains and battery power

• EMG mic

• Memory

Please note that when used with the factory default configuration:

• The background music (BGM) is muted when no spare power amplifier is connected. Disabling the spare power amplifier supervision or overall supervision restores the BGM.

• The BGM will not be present in non-selected zones during a call. If this is desired, connect a spare/call power amplifier and switch the system to 2-channel mode.

Thank you for choosing a Bosch Security Systems product.

en | 4

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Table of Contents en | 5

Table of Contents

Important Safeguards ………………………………………………………………………………………………………………………………..3

Important Notices ……………………………………………………………………………………………………………………………………….4

Table of Contents ……………………………………………………………………………………………………………………………………….5

1.

Introduction ………………………………………………………………………………………………………………………………………………..9

1.1

Purpose ……………………………………………………………………………………………………………………………………………………………….9

1.2

Digital document …………………………………………………………………………………………………………………………………………………9

1.3

Intended audience ………………………………………………………………………………………………………………………………………………9

1.4

Related documentation ……………………………………………………………………………………………………………………………………….9

1.5

Alerts ……………………………………………………………………………………………………………………………………………………………………9

1.6

Signs ……………………………………………………………………………………………………………………………………………………………………9

1.7

Conversion tables ……………………………………………………………………………………………………………………………………………. 10

2.

System Overview ……………………………………………………………………………………………………………………………………. 11

2.1

Voice Alarm System ………………………………………………………………………………………………………………………………………… 11

2.1.1

Introduction …………………………………………………………………………………………………………………………………………………. 11

2.1.2

Application types ………………………………………………………………………………………………………………………………………… 11

2.1.3

Application areas ………………………………………………………………………………………………………………………………………… 11

2.1.4

Plena ……………………………………………………………………………………………………………………………………………………………. 11

2.2

Basic system ……………………………………………………………………………………………………………………………………………………. 11

2.3

Voice alarm controller ………………………………………………………………………………………………………………………………………. 12

2.3.1

Introduction …………………………………………………………………………………………………………………………………………………. 12

2.3.2

Hand-held microphone ……………………………………………………………………………………………………………………………….. 12

2.3.3

Internal power amplifier ………………………………………………………………………………………………………………………………. 12

2.3.4

Internal message manager …………………………………………………………………………………………………………………………. 12

2.3.5

Supervision …………………………………………………………………………………………………………………………………………………. 12

2.3.6

Overview ……………………………………………………………………………………………………………………………………………………… 12

2.4

Call station ……………………………………………………………………………………………………………………………………………………….. 15

2.4.1

Introduction …………………………………………………………………………………………………………………………………………………. 15

2.4.2

Overview ……………………………………………………………………………………………………………………………………………………… 16

3.

Installation ………………………………………………………………………………………………………………………………………………. 17

3.1

Introduction ………………………………………………………………………………………………………………………………………………………. 17

3.2

Requirements …………………………………………………………………………………………………………………………………………………… 17

3.3

Unpacking ………………………………………………………………………………………………………………………………………………………… 17

3.4

CD-ROM ………………………………………………………………………………………………………………………………………………………….. 17

3.5

Hardware installation ……………………………………………………………………………………………………………………………………….. 17

3.6

Emergency microphone …………………………………………………………………………………………………………………………………… 18

3.7

BGM inputs ……………………………………………………………………………………………………………………………………………………… 18

3.8

Call station ……………………………………………………………………………………………………………………………………………………….. 19

3.9

External power amplifier …………………………………………………………………………………………………………………………………… 19

3.10 Loudspeakers …………………………………………………………………………………………………………………………………………………… 20

3.11 Volume overrides ……………………………………………………………………………………………………………………………………………… 21

3.12 Line output ……………………………………………………………………………………………………………………………………………………….. 23

3.13 Mic/line input with VOX functionality ………………………………………………………………………………………………………………. 24

3.14 Status output contacts ……………………………………………………………………………………………………………………………………. 25

3.15 Power ……………………………………………………………………………………………………………………………………………………………….. 25

3.15.1 Introduction …………………………………………………………………………………………………………………………………………………. 25

3.15.2 Mains power ……………………………………………………………………………………………………………………………………………….. 25

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Table of Contents en | 6

3.15.3 Back-up power ……………………………………………………………………………………………………………………………………………. 26

4.

Configuration ………………………………………………………………………………………………………………………………………….. 27

4.1

Introduction ………………………………………………………………………………………………………………………………………………………. 27

4.2

System settings ……………………………………………………………………………………………………………………………………………….. 27

4.2.1

Introduction …………………………………………………………………………………………………………………………………………………. 27

4.3

Monitor ……………………………………………………………………………………………………………………………………………………………… 27

4.4

APR mode ………………………………………………………………………………………………………………………………………………………… 27

4.5

Supervision ………………………………………………………………………………………………………………………………………………………. 28

4.5.1

Introduction …………………………………………………………………………………………………………………………………………………. 28

4.5.2

Overview ……………………………………………………………………………………………………………………………………………………… 28

4.5.3

Processor supervision ………………………………………………………………………………………………………………………………… 28

4.5.4

Message supervision ………………………………………………………………………………………………………………………………….. 29

4.5.5

Line supervision ………………………………………………………………………………………………………………………………………….. 29

4.5.6

Emergency microphone ……………………………………………………………………………………………………………………………… 29

4.5.7

Mains power supervision ……………………………………………………………………………………………………………………………. 29

4.5.8

Battery supervision ……………………………………………………………………………………………………………………………………… 29

4.5.9

Internal power amplifier supervision …………………………………………………………………………………………………………… 29

4.5.10 External power amplifier supervision ………………………………………………………………………………………………………….. 29

4.5.11 1 channel and 2 channel operation ……………………………………………………………………………………………………………. 30

4.6

VOX configuration ……………………………………………………………………………………………………………………………………………. 30

4.6.1

Introduction …………………………………………………………………………………………………………………………………………………. 30

4.6.2

Vox ………………………………………………………………………………………………………………………………………………………………. 31

4.6.3

Speech filter ………………………………………………………………………………………………………………………………………………… 31

4.6.4

Phantom power …………………………………………………………………………………………………………………………………………… 31

4.7

Call station ……………………………………………………………………………………………………………………………………………………….. 31

4.7.1

Introduction …………………………………………………………………………………………………………………………………………………. 31

4.7.2

Call station ID ……………………………………………………………………………………………………………………………………………… 31

4.7.3

Sensitivity ……………………………………………………………………………………………………………………………………………………. 32

4.7.4

Speech filter ………………………………………………………………………………………………………………………………………………… 32

4.7.5

Termination ………………………………………………………………………………………………………………………………………………….. 32

5.

Operation ………………………………………………………………………………………………………………………………………………… 33

5.1

Switch on …………………………………………………………………………………………………………………………………………………………. 33

5.2

Switch off …………………………………………………………………………………………………………………………………………………………. 33

5.3

Calibration ………………………………………………………………………………………………………………………………………………………… 33

5.4

Background music …………………………………………………………………………………………………………………………………………… 33

5.4.1

Introduction …………………………………………………………………………………………………………………………………………………. 33

5.4.2

Select BGM source ……………………………………………………………………………………………………………………………………. 33

5.4.3

Select zones ……………………………………………………………………………………………………………………………………………….. 34

5.4.4

Adjust volume ……………………………………………………………………………………………………………………………………………… 34

5.4.5

Adjust frequencies ……………………………………………………………………………………………………………………………………… 34

5.5

Business calls ………………………………………………………………………………………………………………………………………………….. 35

5.5.1

Introduction …………………………………………………………………………………………………………………………………………………. 35

5.5.2

Select zones ……………………………………………………………………………………………………………………………………………….. 35

5.5.3

Make the announcement ……………………………………………………………………………………………………………………………. 35

5.6

Emergency state ………………………………………………………………………………………………………………………………………………. 36

5.6.1

Introduction …………………………………………………………………………………………………………………………………………………. 36

5.6.2

Enter the emergency state …………………………………………………………………………………………………………………………. 36

5.6.3

Acknowledge the emergency state ……………………………………………………………………………………………………………. 36

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Table of Contents en | 7

5.6.4

Exit the emergency state …………………………………………………………………………………………………………………………….. 36

5.6.5

Distribute live speech …………………………………………………………………………………………………………………………………. 36

5.6.6

Distribute the alert message ………………………………………………………………………………………………………………………. 38

5.6.7

Distribute the alarm message …………………………………………………………………………………………………………………….. 39

5.7

Fault state ………………………………………………………………………………………………………………………………………………………… 39

5.7.1

Introduction …………………………………………………………………………………………………………………………………………………. 39

5.7.2

Acknowledge the fault state ………………………………………………………………………………………………………………………. 39

5.7.3

Reset the fault state ……………………………………………………………………………………………………………………………………. 39

5.7.4

Fault indicators ……………………………………………………………………………………………………………………………………………. 40

6.

Technical data …………………………………………………………………………………………………………………………………………. 43

6.1

LBB1956/00 ……………………………………………………………………………………………………………………………………………………. 43

6.1.1

Electrical ……………………………………………………………………………………………………………………………………………………… 43

6.1.2

Performance ……………………………………………………………………………………………………………………………………………….. 43

6.1.3

Interconnection …………………………………………………………………………………………………………………………………………… 43

6.1.4

Environmental conditions ……………………………………………………………………………………………………………………………. 43

6.1.5

General ……………………………………………………………………………………………………………………………………………………….. 43

6.2

LBB1990/00 ……………………………………………………………………………………………………………………………………………………. 43

6.2.1

Electrical ……………………………………………………………………………………………………………………………………………………… 43

6.2.2

Message manager ………………………………………………………………………………………………………………………………………. 44

6.2.3

Internal power amplifier ………………………………………………………………………………………………………………………………. 44

6.2.4

Interconnection …………………………………………………………………………………………………………………………………………… 44

6.2.5

Loudspeaker outputs ………………………………………………………………………………………………………………………………….. 44

6.2.6

Overrides …………………………………………………………………………………………………………………………………………………….. 44

6.2.7

Trigger outputs ……………………………………………………………………………………………………………………………………………. 44

6.2.8

Trigger inputs/24 V DC out ……………………………………………………………………………………………………………………….. 45

6.2.9

Mic/line input with VOX functionality …………………………………………………………………………………………………………. 45

6.2.10 BGM ……………………………………………………………………………………………………………………………………………………………. 45

6.2.11 Line out ……………………………………………………………………………………………………………………………………………………….. 45

6.2.12 External power amplifier ……………………………………………………………………………………………………………………………… 45

6.2.13 Environmental conditions ……………………………………………………………………………………………………………………………. 45

6.2.14 General ……………………………………………………………………………………………………………………………………………………….. 45

7.

Glossary …………………………………………………………………………………………………………………………………………………… 47

8.

Product Index ………………………………………………………………………………………………………………………………………….. 49

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Table of Contents

Intentionally left blank.

en | 8

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Introduction en | 9

1 Introduction

1.1 Purpose

The purpose of the Basic System Manual is to provide information that is required to install, configure and operate a basic Plena Voice Alarm System. By definition, such a system is installed, configured and operated without a PC.

1.6 Signs

Except for note alerts, the nature of the effect that can be caused when the alert is not observed, is indicated using a sign. For note alerts, the sign provides more information about the note itself. In this manual, the following signs are used in combination with alerts:

Note

General sign for notes.

The Basic System Manual is also available as a digital document in the Adobe Portable Document Format

(PDF). All references to pages, figures, tables, etc. in this digital document contain hyperlinks to the referenced location.

Note

Consult the indicated source of information.

Caution, Warning, Danger

General sign for cautions, warnings and dangers.

The Basic System Manual is intended for installers and users of a basic Plena Voice Alarm System. Installers and users of extensive systems should refer to the

Installation and User Instructions (see section 1.4).

The following related documents are available:

• Plena Voice Alarm System Installation and User

Instructions (9922 141 1037x).

• Plena Voice Alarm System Configuration Software

Manual (9922 141 1038x).

1.5 Alerts

In this manual, four types of alerts are used. The alert type is closely related to the effect that may be caused when it is not observed. These alerts — from least severe effect to most severe effect — are:

Note

Alert containing additional information. Usually, not observing a note alert does not result in damage to the equipment or personal injuries.

Caution

The equipment can be damaged if the alert is not being observed.

Warning

Persons can be (severely) injured or the equipment can be seriously damaged if the alert is not being observed.

Danger

Not observing the alert can result in death.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Caution, Warning, Danger

Risk of electric shock.

Caution, Warning, Danger

Risk of electrostatic discharges.

Plena Voice Alarm System | Basic System Manual | Introduction

In this manual, SI units are used to express lengths, masses, temperatures etc.. These can be converted to non-metric units using the information provided below.

table 1.1: Conversion of units of length

1 in =

1 in =

25.4 mm

2.54 cm

1 mm =

1 cm =

1 ft =

1 mi =

0.3048 m

1.609 km

1 m =

1 km =

0.03937 in

0.3937 in

3.281 ft

0.622 mi

table 1.2: Conversion of units of mass

1 lb = 0.4536 kg 1 kg = 2,2046 lb

table 1.3: Conversion of units of pressure

1 psi = 68.95 hPa 1 hPa = 0.0145 psi

Note

1 hPa = 1 mbar.

°

F

=

9

5

⋅ °

C

+ 32

°

C

=

5

9

⋅ ( °

F

32

) en | 10

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | System Overview en | 11

2

2.1.1

System Overview

Introduction

The Plena Voice Alarm System is a public address and voice alarm system in which all the necessary features for compliance to evacuation standards such as

IEC60849, NEN2575 and BS5839/8 are integrated.

2.1.4

Plena

The Plena Voice Alarm System is part of the Plena product range. Plena provides public address solutions for places where people gather to work, worship, trade or simply enjoy themselves. It is a family of system elements that are combined to create public address systems tailored for virtually any application. The range includes mixer, pre, system and power amplifiers, a source unit, digital message manager, feedback suppressor, conventional and PC call stations, an ‘All-in-

One’ system and a voice alarm system. Each element is designed to complement all others thanks to matched acoustical, electrical and mechanical specifications.

2.1.2

Application types

Typically, the Plena Voice Alarm System is used to create small systems that must comply to evacuation standards, medium-sized systems in which one call channel is enough and large systems that consist of many small zones.

2.1.3

Application areas

The application areas of the Plena Voice Alarm System include:

• Supermarkets, shops

• Factories

• High-rise buildings

• Office buildings

• Schools

• Recreational facilities

• Hotels

• Small airports

As mentioned before, the scope of this manual is a basic system. By definition, a basic system is installed, configured and operated without a PC. Such a system can only consist of:

• 1x LBB1990/00 Voice Alarm Controller (required).

• 1x LBB1956/00 Call Station (optional).

LBB1956/00

LBB1990/00

figure 2.1: Basic system

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | System Overview en | 12

2.3 Voice alarm controller

2.3.1

Introduction

The LBB1990/00 Voice Alarm Controller is the heart of the Plena Voice Alarm System. The voice alarm controller distributes emergency calls, business calls as well as background music (BGM) to up to 6 loudspeaker zones.

2.3.4

Internal message manager

The voice alarm controller has an internal message manager, which maps wave files (.wav) to messages that can be played by the Plena Voice Alarm System.

2.3.5

Supervision

All necessary supervision features for compliance to evacuation standards are integrated into the voice alarm controller. If supervision is enabled and a fault is detected, the voice alarm controller lights a LED on its front panel that indicates the cause of the fault.

figure 2.2: Voice Alarm Controller

Note

When the voice alarm controller has been purchased in the Asian-Pacific Region, the emergency button has a different cover.

2.3.2

Hand-held microphone

The voice alarm controller is equipped with a hand-held microphone, which can be used to make emergency calls.

2.3.3

Internal power amplifier

The voice alarm controller has a 240 W internal power amplifier, which can be used in 1-channel or 2-channel mode. In the 1-channel mode, all calls and BGM are amplified by the internal power amplifier. If desired, an external power amplifier can be connected for spare switching. In the 2-channel mode, the BGM is amplified by the internal power amplifier, whereas the calls are amplified by an external power amplifier.

2.3.6

Overview

See figure 2.3 for an overview of the controls, connections and indicators on the voice alarm controller:

1 Power LED/VU Meter — A combined power indicator and VU meter. The green power LED is lit if the voice alarm controller is connected to the mains or back-up power and switched on. The VU meter indicates the master VU level: 0 dB (red), — 6 dB, -20 dB (yellow).

2 Fault indicators — Twelve yellow system fault

LEDs (Processor reset, Network, Call/EMG, Music/

Spare , Ground short, Input, Mains, Battery, Message,

EMG mic

, RCP and Router) and twelve yellow loudspeaker line fault LEDs. Fault indication is only

possible if supervision is enabled (see section 5.7). If

supervision is disabled, the yellow Disabled LED is lit.

3 Fault state buttons — Two buttons to acknowledge

(Ack) and reset (Reset) the fault state (see section

5.7).

4 Emergency state buttons — Two buttons to acknowledge (Ack) and reset (Reset) the emergency

state (see section 5.6).

5 Emergency call zone selectors — Six buttons to select the zones to which the emergency call must be

distributed (see section 5.6). Each button has a green

and a red LED. The six red LEDs indicate the zones that are selected for the emergency call. The six green LEDs indicate the zones in which a business call is running.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | System Overview en | 13

1 2 3 4 5

Plena Voice Alarm Controller

0 dB

-6dB

-20dB

Fault Indicators

Processor reset

Network

Call/EMG

Music/Spare

Ground short

Input

Mains

Battery

Message

EMG mic

RCP

Router

A

Disabled

B

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

Alert message

EMG mic

Alarm message

All call

Indicator test

Fault

Ack

Reset

EMG

Select

CD/Tuner Aux

Zone select

Zone1

Zone select

+

Zone2

+

0

Zone3

17 16 15 14

13

12 11

10

9 8 7 6

Zone4 Zone5

18 19 20 21

Zone6

Alarm

22 23 24 25 26 27 28 29 30 31

Int Booster

Ext Booster

A

Z1

Z2

Z3

Z4

Z5

Z6

Ext

B ooster

In

100V

0

100V

0

100V

0

100V

0

100V

0

100V

0

100V

0

DC In 24V

1 Channel

BGM/ C all

N.C ./Spare

2 Channel

BGM/ Spare

C all

Override/Trigger Output

B

100V

0

100V

0

100V

0

100V

0

100V

0

100V

0

100V

70 V

0

10 0V

Z1

Z1

24V

Z2

Z3

Z4

Z5

Z6

Z2

Z3

Z4

Z5

Z6

TRG 1

Int

B ooster

Out

C all out

GND

NC

COM

NO

EM G

NC

COM

NO

Fault

NC NO

COM

NC

COM

NO

C all

NC

24V

NO

Volume Override

TRG2

Out

External Booster

Trigger input/24V DC out

Emergency

1 2 3 4 5 6

24V

DC out

Business

1 2 3 4 5 6

VO X

Switch

10 k 10 k

1 2 3 4 5 6

24V

DC out

1 2 3 4 5 6

VO X Switch

In

CD/Tuner AU X PC

L

R

Call station

1

For ser vice only

SEL1

SEL0

Firmware

Upgrade

Off

2

On

Monitor

APR mode

Supervision

2ch operation

Reserved

Impedance

Calibration

GND

Mic/Line

Vox

115V~

230V~

LBB 1 990 /00 8900 199 0 0001

Plena Voice Alarm Controller

Max. output power 360W

Rated output power 240W

115-230V~, 50/60Hz

S/N.

Design & Quality

The Netherlands

N6 63

Apparatus delivered

C onnected for 230V~

Power

RS232

USB

Off

On

Vox

Speech filter

Phantom power

Off

On

EMG. Mic

Digital

Mess age

Monitoring

Speaker

Reserved

Line fuse

T6.3L250V for230V AC

T10L250V for115V AC

Remote Control Panel

1

2

Router

Rated input power :760VA

W arning

This apparatus must be earthed

47 46 45 44 43 42 41 40 39

figure 2.3: Front and rear views of the voice alarm controller

6 BGM zone selectors — Six buttons to select the

zones to which the BGM is distributed (see section

5.4). Each button has a green LED and a rotary

knob. The six green LEDs indicate the zones to which BGM is distributed. The six rotary knobs are local volume controls that can be used to adjust the volume of the BGM in each zone.

38 37 36 35 34 33 32

7 BGM master volume control — A rotary knob to

set the master volume of the BGM (see section 5.4).

8 BGM source selector — A button to select the

BGM source (CD/Tuner or Aux). The selected source

is indicated with a green LED (see section 5.4).

9 BGM tone controls — Two rotary knobs to control the high and low frequencies of the BGM (see

section 5.4).

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | System Overview en | 14

10 All call button — A button to select all zones. This button is only available in the emergency state (see

section 5.6).

11 Indicator test button — A button to test all LEDs on the front panel of the voice alarm controller. All

LEDs are lit as long as the button is pushed (see

section 5.7).

12 Emergency button — A push button to put the

system in the emergency state (see section 5.6).

13 Alert message button — A button to select the alert message. This button is only available in the

emergency state (see section 5.6).

14 Alarm message button — A button to select the default alarm message. This button is only available

in the emergency state (see section 5.6).

15 Microphone socket — A socket to connect the

hand-held emergency microphone (see section 3.6).

16 Bracket — A bracket for the hand-held emergency microphone that is supplied with the voice alarm controller.

17 Monitoring speaker — Built-in monitoring speaker.

18 Zone outputs — Six zone outputs to connect loudspeakers to the voice alarm controller. Each zone output consists of two loudspeaker line outputs

(see section 3.10).

19 Override outputs — Six volume override outputs to override local volume controls in each zone (see

section 3.11).

20 Status outputs — Three status outputs to send the status of the Plena Voice Alarm System to third party

equipment (see section 3.14).

21 Trigger inputs/24 V DC output — Twelve trigger inputs to receive signals from third party equipment and one 24 V(DC) output. Except for the VOX switch input and the 24V DC out output, these must be configured with the configuration software and

are therefore not used in basic systems (see section

3.13).

22 Call station sockets — Two redundant RJ45 sockets to connect call stations (LBB1956/00) to the

voice alarm controller (see section 3.8).

23 Service settings — A set of DIP switches to service the voice alarm controller. Do not change the positions of the switches.

24 Calibration switch — A switch to calibrate the impedances of the loudspeaker lines for loudspeaker

supervision (see section 4.5.5.3).

25 Configuration settings — A set of DIP switches to

configure the voice alarm controller (see section 4.2).

26 PC socket — A USB socket to connect the voice alarm controller to a PC. Not for use in basic systems.

27 Emergency microphone volume control — A rotary knob to set the volume of the hand-held emergency microphone.

28 Reserved

29 Reserved

30 Voltage selector — A voltage selector to select the

local mains voltage (see section 3.15).

31 Power switch — A switch to switch the voice alarm

controller on and off (see section 5.1).

32 Ground — A connection to electrically ground the voice alarm controller.

33 Mains power inlet — A socket to connect the voice

alarm controller to the mains power (see section

3.15).

34 Router socket — An RJ45 socket to connect voice alarm routers (LBB1992/00) to the voice alarm controller. Not for use in basic systems.

35 Remote control panel socket — Two redundant

RJ45 sockets to connect remote control panels

(LBB1996/00, LBB1997/00) to the voice alarm controller. Not for use in basic systems.

36 Monitoring speaker volume control — A rotary knob to set the volume of the monitoring loudspeaker.

37 Digital message volume control — A rotary knob to set the volume of the digital business messages. This volume control does not influence the volume of the emergency messages.

38 Mic/line input with VOX functionality — An

XLR socket and a 6.3 mm jack with voice-activated

(VOX) functionality to connect a microphone or line

input to the voice alarm controller (see section 3.13).

The VOX settings are configured with the DIP

switches and the source switch (see section 4.6).

39 PC Call station input — An input to connect a PC call station. Not for use in basic systems.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | System Overview en | 15

40 BGM inputs — Two inputs to connect background music sources. Each input consists of two cinch

sockets (see section 3.7).

41 Line output — A line output to connect an external recording device to record the audio of the Plena

Voice Alarm System (see section 3.12).

42 External power amplifier (output) — An XLR socket to connect an external power amplifier (see

section 3.9). This socket is used in combination with

the external power amplifier input (no. 47).

43 Trigger outputs — Two general purpose trigger outputs. Not for use in basic systems.

44 Internal power amplifier output — Three pins that provide the 100 V audio signal of the internal power amplifier of the voice alarm controller.

45 Call output — An output that provides the call audio of the Plena Voice Alarm System.

46 Back-up power inlet — An inlet to connect a backup power supply to the voice alarm controller (see

section 3.15).

47 External power amplifier (input) — An input to

connect an external power amplifier (see section 3.9).

These pins are used in combination with the external

power amplifier output (no. 42).

2.4.1

Introduction

The LBB1956/00 Call Station can be connected to the

LBB1990/00 Voice Alarm Controller to make business calls. The call station is connected to the voice alarm controller using standard Cat-5 Ethernet cable.

figure 2.4: Call Station

The call station is not supervised. For compliance to evacuation standards, the Plena Voice Alarm System disables the call station during emergency calls.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | System Overview en | 16

2.4.2

Overview

See figure 2.5 for an overview of the controls, indicators

and connectors on the call station:

1 Power indicator — A green LED to indicate that the call station is powered on.

2 Zone selection buttons — Six buttons to select the zones to which the business call is distributed (see

section 5.5). Each button has a green LED, which

indicates the zones to which the business call is distributed.

3 ‘All call’ selector — A button to select all zones

(see section 5.5).

4 Push-to-talk button — A push-to-talk (PTT) button to start the business call.

5 Status indicators — Three LEDs that indicate the

status of the call station (see section 5.5).

6 Keypad connector — A connector to connect call station keypads (LBB1957/00) to the call station.

7 Configuration settings — A set of DIP switches to

configure the call station (see section 4.7).

8 Power supply inlet — A socket to connect a

24 V(DC) power supply (see section 3.8).

9 System sockets — Two redundant RJ45 sockets to connect the call station to the voice alarm controller

(LBB1990/00, see section 3.8).

Plena

1

2

3

5

4

figure 2.5: Top and bottom views of the call station

6 7

8

9

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 17

3 Installation

3.1 Introduction

This chapter describes how to install a basic Plena

Voice Alarm System.

3.2 Requirements

Before starting to install the basic system, check if the installation site(s) for the voice alarm controller and call station meet the environmental, electrical and physical

requirements that are listed in chapter 6.

3.3 Unpacking

The voice alarm controller and the call station are shipped in boxes. For the contents of these boxes, see

table 3.1 and table 3.2.

3.4 CD-ROM

The CD-ROM in the box of the voice alarm controller contains:

• Plena Voice Alarm System configuration software

• Audio tools (e.g. converters)

• Default messages and chimes

• Plena info

• Basic System Manual

• Installation and User Instructions

• Bosch data book

The voice alarm controller is suitable for table-top and

19-inch rack-mounting installation. Two brackets for rack-mounting are supplied. See figure 3.1 for installation details.

Note

Always compare the contents of a shipment with the descriptions on the shipment documents.

Plena

0 dB

-6dB

-20dB

Voice

Alarm

Fault In dicator s

Proces

Netwo sor res rk

Call/E

M G et

Music/S

Groun pare d short

Contro ller

Mains

Battery

Messa ge

EMG

RCP

Route mic

A

Alert m essage

EMG mic

Alarm messa ge

Disable

B d

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

All call

Fault

Ack EMG

Reset

+

Select

CD/Tu ner

Aux

Zone select

Zone1

Zone select

Zone2

+

0

Zone3

Zone4

Zone5

Zone6

Alarm

table 3.1: LBB1990/00 contents

Description

Voice alarm controller

Safety instructions

Basic system manual

CD-ROM (see section 3.4)

Power cord

Emergency microphone

19” rack-mounting brackets

USB cable

Quantity

1 x

1 x

1 x

1 x

1 x

1 x

2 x

1 x

figure 3.1: Brackets for rack-mounting

Make sure that there is a free space of at least 100 mm on both sides of the unit for ventilation. The voice alarm controller has an internal fan, which is regulated to keep the temperature inside the unit within the safe operating area.

table 3.2: LBB1956/00 contents

Description

Call station

Cat-5 cable

Quantity

1 x

1 x

Caution

Keep the equipment boxed until the moment of installation. Boxed equipment is relatively well protected.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 18

The voice alarm controller has one connector for an emergency microphone. A hand-held emergency microphone is supplied with the voice alarm controller.

See figure 3.2 for installation details. Turn the lock ring clockwise to lock the plug.

The voice alarm controller has 2 BGM inputs (see figure

3.3 and table 3.3). Each BGM input has a double cinch socket. To these cinch outputs, a background music source can be connected (e.g. a PLN-DVDT Plena

DVD Tuner). The signals connected to the L (left) and R

(right) cinch sockets are mixed to form a single input signal.

Plena

0 dB

-6dB

-20dB

Voice

Alarm

Contro ller

Fault In dicator

Proces

Netwo

Call/E sor res

M G et

Music/ Spare

Groun d short

Input

Mains

Battery

Messag

EMG

RCP

Router mic

Alert m essag

EMG mic

Alarm messa ge

Disable

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

All call

Indicato r test

Fault

+

Ack

Reset

EMG

Select

Aux

Zone select

Zone1

Zone select

Zone2

+

Zone3

Zone4

Zone5

Zone6

Alarm

LBB1990/00

LBB1990/00

In

figure 3.2: Connecting the emergency microphone

CD/Tuner

AUX

figure 3.3: BGM inputs table 3.3: BGM inputs

Input Source

CD/Tuner

AUX

CD or tuner

Auxiliary source

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 19

The call station can be connected to one of the shielded

RJ45 call station sockets on the voice alarm controller with a Cat-5 Ethernet cable. See figure 3.4 for connection details.

The voice alarm controller has 1 external power amplifier output (line level, 1 V) and 1 external power amplifier input (100 V) to connect an external power amplifier (see figure 3.6). The function of the external power amplifier (e.g. a PLN-1P120 Plena Power

Amplifier) depends on the channel mode for which the

voice alarm controller is configured (see section 4.5.11).

6

VOX tch

10k

10k

5

6 24V

DC ou t

5

6

VOX Sw itch

Call st ation

1

2

For ser vice on ly

SEL1

SEL0

Firmw

Upgrad e

Off

2

S

On

Impeda

Calibr nc

Z5 100V

Z6 100V

Ext

Booste 100V

DC In

24V

Int Bo

Ext B oster ooste

Z1 100V

A

1 Chan nel

BGM /Call

N.C./S pare

Z2

100V

Z3 100V

Z4 100V

2 Chan

BGM

Call nel

/Spare

B Overrid e/Trigg

100V

100V

Z1 Z1

100V

Z2

Z2

Z3

24V

100V

Z3 Z4

Z4 Z5

100V

100V

Z5

Z6

TRG

Z6

100V

70V Int

Booste

Out

100V

Call ou

GND

NC

COM

NO

EMG

NC

Fault

NC

CO

NO

COM

NO

NC

24V

Call

NO Volum e Over ride

TRG2

Out

Trigge r inpu

Emerg ency t/24V

DC ou

Busin ess

Externa l Boos ter

In

CD/Tu ner

AUX

VOX S witch

PC

Call sta tion

For ser vice on

SEL1

SEL0

Firmw

Upgrad

Off

On

Monito

APR

Superv mode

2ch op ision

LBB ance

Calibra tion

GND

Mic/L ine

Vox

Off

On

Vox

Spee

Off ch filte m pow

On

LBB 1

Plena

Max. o

Rated

S/N.

990/0

Voice Alarm utput p

0V~, 5 power 60W

Design

0/60H

The N ower 3 etherla & Qua lity nds ler

N663

USB

01

115V~

230V~

Appara

Conne tus deli cted fo vered r 230V

Line fu

T6.3L2

T10L2 se

50V fo

50V fo

Remote

Contro

Firema n’s pan

LBB19 r230V

AC

AC l Panel

94

Power

Rated input p ower:7

60VA

Digital

Messa ge

Monito

Speake ring

Router

This ap paratu s must be eart hed

LBB1990/00

LBB1990/00

LBB1956/00

Plena na

Ple

Z2

100V

0

100V

Z3

Z4

0

100V

0

100V

Z5

Z6

Ext

Booster

In

0

100V

0

100V

0

DC In 24V

0

Z2

100V

0

100V

Z2

Z3

Z3

Z4

0

100V

Z5

Z4

0

100V

Z6

Z5 TRG 1

0

100V

0

100V

Z6

70V

0

Int

Booster

Out

100V Call out

GND

NO

NC

COM

NO

Fault

COM

NC

COM

NO

Call

NC

24V

NO

Volume Override

TRG2

Out

External Booster

figure 3.4: Connecting a call station

If the cable between the call station and the voice alarm controller is longer than 100 m, the call station must be connected to a 24 V(DC) power source. See figure 3.5 for connection details.

LBB1956/00 na

Ple

+

1

3

G ND

2

G ND

1

3

+

2 line in line out

100V 70V 0

Plena

figure 3.5: Connecting a power supply

Bosch Security Systems | 2005-04 | 9922 141 10364en

PLN-1P120

figure 3.6: Connecting an external power amplifier

Plena Voice Alarm System | Basic System Manual | Installation en | 20

3.10 Loudspeakers

The voice alarm controller has 6 zone outputs (Z1 to

Z6 ). Each zone output consists of 2 redundant loudspeaker lines (line A and line B). Normally, calls and BGM are distributed to a zone over both loudspeaker lines. If one of the loudspeaker lines of a zone fails, it is still possible to distribute calls and BGM to the zone over the remaining loudspeaker line (see figure 3.7).

If it is necessary to detect the removal or failure of a single loudspeaker, the following is advised:

• Do not connect more than 5 loudspeakers to the same loudspeaker line (line A or line B). Field tests have shown that the impedance of loudspeakers and loudspeaker lines varies with temperature and age.

The limit of 5 loudspeakers is set due to this variation. In a more stable environment, the number of loudspeakers can be higher.

• Make sure that all loudspeakers connected to the same loudspeaker line have the same impedance.

LBB1990/00

Note

The impedance measurement of the Plena Voice

Alarm System has an accuracy better than 2%.

The system only generates a fault if the line impedance difference is greater than 15%

(default accuracy).

A

Ext

Booster

In

Z1

Z2

Z3

Z4

Z5

Z6

100V

0

100V

0

100V

0

100V

0

100V

0

100V

0

100V

0

DC In 24V

BGM/

B

0

100V

0

100V

0

100V

0

100V

70V

0

100V

0

100V

0

100V

Z1

Z2

Z3

Z4

Z5

Z6

Int

Booster

Out

100V Call out

Z6

Z5

Z4

Z3

6A

5A

4A

6B

5B

4B

Note

The maximum load for the internal power amplifier of the voice alarm controller is 240 W.

However, if the voice alarm controller is used in

2-channel mode and an external 480 W amplifier is connected to it, the maximum loudspeaker load can be 480 W at 100 V. This is because in 2-channel mode, the internal power amplifier of the voice alarm controller is used for BGM only and distributes BGM at

-3 dB, from which follows that the maximum power output is 240 W at 70 V and that the loading caused by 100 V loudspeakers at 70 V is also 240 W. The external amplifier is used for calls only with 480 W output power and 100 V loudspeaker line voltage.

3A 3B

Z2

2A 2B

Z1

1A 1B

figure 3.7: Connecting loudspeaker zones

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 21

The voice alarm controller has 6 override outputs; 1 for

each zone in the system (see figure 3.8). These are

suitable for 4-wire override (24 V) as well as for 3-wire override.

Internally, the positive override pins (Z+) are all connected to either the NC or the NO contact of the

Volume Override

output (see figure 3.9). The negative

override pins (Z-) are all connected to earth.

Z1

+

_

Note

By default, the voice alarm controller is configured for 4-wire (24 V), power-saving override, see situation I in figure 3.10.

Z2

+

_

LBB1990/00

Z3

+

_

Z4

+

_

Override/Trigger Output

Z3

Z4

Z5

Z1

24V

Z2

Z6

TRG 1

NC

COM EMG

NO

NC

COM

NO

Fault

NC NO

COM

NC

COM

NO

Call

NC

24V

NO

Volume Override

TRG2

figure 3.8: Override outputs

Z5

+

_

Z6

+

_

figure 3.9: Volume override contacts

NO NC

Normally, when there are no active calls, the Z+ pins are internally connected to the NC contact of the

Volume Override . At the moment a call is started in a zone, the Z+ pin of the zone is internally connected to the NO contact of the Volume Override. So, the NC and the NO contacts determine which voltage is supplied to the positive pins of the override outputs (Z+).

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 22

See figure 3.10, situation I for an example of a fail-safe

4-wire volume override:

• Connect the NO contact of the Volume Override to the 24V contact of the Volume Override.

See figure 3.10, situation II for an example of a power-saving 4-wire volume override:

• Connect the NC contact of the Volume Override to the 24V contact of the Volume Override.

LBB1990/00

NC

NO

Override/Trigger Output

Z1

24V

Z2

Z3

Z4

Z5

Z6

G 1

NC

COM

NO

EM

NC

COM

NO

Fault

NC NO

COM

NC

COM

NO

Call

NC

24V

NO

Volume Override

TRG2

100V

0V

24V

0V

Override/Trigger Output

Z1

24V

Z2

Z3

Z4

Z5

Z6

G 1

NC

COM

NO

EM

NC

COM

NO

Fault

NC NO

COM

NC

COM

NO

Call

NC

24V

NO

Volume Override

TRG2

100V

0V

24V

0V

figure 3.10: 4-wire volume override

NO

NC

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 23

To create a 3-wire volume override, see figure 3.11:

Note

It is not possible to use 3-wire volume override in a basic system, because it must be enabled using the configuration software. See the

Installation and User Instructions

(9922 141 1037x) and the Configuration

Software Manual (9922 141 1038x) for more information.

Note

It is not possible to use 3-wire volume override in combination with redundant loudspeaker lines

(line A and B, see figure 3.7). If redundant loudspeaker lines are needed, use 4-wire volume override (see figure 3.10).

• Connect the 100V output of loudspeaker line A to the 100 V input of the volume control.

• Connect the 100 V/0 V (CALL/RTN) of the transformer to the 100V output of loudspeaker line

B

.

• Connect the 0 output of loudspeaker line A to the

0 V of the loudspeaker.

• Enable 3-wire volume override in the configuration software.

The voice alarm controller has one line output (see figure 3.12). This output has a double cinch socket. Both cinch sockets contain the same, mono signal, which consists of the current BGM and calls. The line output can be used to connect the voice alarm controller to a recording device (e.g. a tape-deck).

LBB1990/00

Booster

figure 3.12: Line output

In

CD/Tuner

Caution

Make sure that the correct connections have been made and the system is correctly configured.

100V

A

100V

B

0V

A

figure 3.11: 3-wire volume override

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 24

3.13 Mic/line input with VOX functionality

The voice alarm controller has 1 mic/line input with

voice-activated (VOX) functionality (see figure 3.13).

This input has two sockets; one balanced XLR socket and a balanced 6.3 mm jack socket. The signals from both sockets are mixed to form a single input signal.

In basic systems, the default priority of the mic/line input with VOX functionality is 6. This means that it can be used to make business calls (e.g. with a

PLN-MM Plena Message Manager). The input automatically starts a business call if the input is higher than -20 dB (100 mV for line and 100

µ

V for microphone inputs) or if the VOX switch is closed (see

figure 3.14).

LBB1990/00

p

Calibration

GND

Note

In extended systems, the mic/line input with

VOX functionality can also be used to make emergency calls. For example, it can be used to create a supervised link to another emergency sound system (e.g. a Praesideo system). See the Installation and User Instructions

(9922 141 1037x) for more information.

L

Mic/Lin

PC

R

LBB1990/00

figure 3.13: Mic/line input with VOX functionality

1 2 3 4 5 6

24V

DC out

1 2 3 4 5 6

VOX Switch

figure 3.14: Connecting a VOX switch

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 25

3.14 Status output contacts

The voice alarm controller has 3 status output contacts

to indicate the current system state (see figure 3.15).

These are used to send the status of the Plena Voice

Alarm System to third party equipment or to connect sounders or similar indicating devices.

LBB1990/00

3.15 Power

3.15.1

Introduction

The voice alarm controller has the following power connections:

Mains power connection (see section 3.15.2).

Back-up power connection (see section 3.15.3).

3.15.2 Mains power

Proceed as follows to connect the voice alarm controller to the mains power:

1 Select the local mains voltage using the voltage selector on the rear of the voice alarm controller.

Z5

Z6

TR

Z1

Z2

Z3

Z4

NC

COM

NO

EMG

NC

COM

NO

Fault

NC

COM

NO

Call

NC

24V

NO

V olume Overr

TRG2

LBB1990/00

115V~ 230V~

NC

COM

NO

Apparatus delivered

Connected for 230V~

figure 3.15: Status output contacts (default) table 3.4: Status output contact

Contact Description

EMG

Fault

Call

Emergency state. See section 5.6

Fault state. See section 5.7

Call active state.

The status output contacts are internal relays. By default, NC is connected to COM. When the Plena

Voice Alarm System enters one of the states that are

indicated in table 3.4, the relay connects NO to COM.

Power

figure 3.16: Voltage selector table 3.5: Voltage selector

Selector Mains voltage

V(AC)

115

230

100 — 120

220 — 240

Fuse

115 V — 10 AT

230 V — 6.3 AT

Note

The LBB1990/00 Voice Alarm Controller is delivered with the voltage selector in the 230 position.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Installation en | 26

2 Put the correct type of fuse in the voice alarm

controller (see table 3.5).

Note

The LBB1990/00 Voice Alarm Controller is delivered with a T6.3L 250 V fuse for a mains voltage of 220 to 240 V(AC).

3 Connect a locally approved mains cord to the voice

alarm controller (see figure 3.17).

4 Connect the mains cord to a locally approved mains

outlet (see figure 3.17).

3.15.3 Back-up power

The voice alarm controller has a 24 V(DC) input to connect a back-up power supply (e.g. a battery) which powers the system if the mains power is not available.

See figure 3.18 for connection details.

Z6

00V

Booste

In r

0

100V

0

DC In

24V

Z2

Z3

Int Bo

Ext B

Z1 100V

100V

100V oster ooste

A

Z4 100V

Z5

100V

Boos ter 100V

DC In

Z6 100V

24V

BGM /Call

BGM

2 Chan

Call nel

B

100V

100V

Z1

Overrid e/Trigg er Outp ut

24V

Z1

100V

Z2

Z2

Z3

NC

COM

NO

EMG

NC

Fault

NC

COM

NO

100V

100V

Z3

Z4

Z4

Z5

100V

Z5

TRG

Z6

Z6

100V

70V Int

Booste

Out

100V

Call ou

COM

NO

NC

24V

NO

TRG2

Call

Volum

Out e Over ride

GND

Externa l Boos ter

Trigge r input

Emerg

/24V ency DC ou

Busin ess

In

DC ou 24V

Switch VOX

DC ou

24V

CD/Tu ner

AUX

VOX S witch

PC

Call sta tion

For serv ice only

SEL1

SEL0

Firmw

Upgrad are

Off

On

Monitor

APR

Superv

2ch ope

LBB19 ision ration

94

Imped ance tion

GND

Mic/Lin

Vox

Vox

Speec

Phanto h filter m pow

Off

On

Off

On

Plena

Max. o

Rated output

S/N.

Voice utput p

115-2 30V~

Alarm 8900

Contro

60W ller

199 000

01

, 50/6 power

0Hz 240W

Design

The N etherla nds

N663

USB

Line fu

T6.3L2

T10L2

Remote se

50V fo

50V fo

LBB199 r230V r115V

AC

AC

Contro l Panel

115V~

230V~

Appara

Conne tus deli vered r 230

V~

Power

Rated input p ower:7

60VA

Digital

Messa ge

Monito

Router

This ap paratu s must be eart hed

LBB1990/00

00 na Voic e Alarm power

230V

.

8900

Contro ller

/60H z

W

199 000

01

The N etherla nds

N663

USB

115V~

230V~

Firema n’s pan el

Power

Rated input powe r:760VA

T10L25

0V for1

LBB19

94

Line fuse

50V fo r230V

Remot e Cont

15V A

AC

C rol Pan el

Appa

Conn ratus d ected elivere d

V~

Mess age

Monit oring

1

Router

2

DC In

Int Bo

Ext B oster ooste

Z1

Z2

Z3

Z4

Z5

Z6

100V

100V

100V

100V

100V

100V

100V

24V

A

1 Chan

BGM nel

N.C./S /Call pare

2 Chan nel

BGM

Call

/Spare

B

100V

Overrid e/Trigg er Outp ut

Z1 Z1

24V

100V

100V

Z2

Z2

Z3

Z3

Z4

100V

100V

100V

Z4 Z5

100V

70V

Z5

Z6

TRG

100V

Z6

Int

Booste

Out

Call ou

GND

NC

EMG

Out

NC

COM

NO

NC

Fault

COM

Call

COM

NO

NC

24V

NO

TRG2

Volum e Over ride

NO

Extern al Boo ster

Trigge

Emerg r inpu ency t/24V

DC ou

Busin ess

In

24V

DC ou

VOX

Switch

24V

DC ou

CD/Tu ner

AUX

VOX S witch

PC

Call sta tion

For ser vice on

Off

SEL1

SEL0 are

Upgrad

Monito

APR

Super mode

2ch op

LBB19 vision

94

On

Imped ance tion

GND

Mic/Line

Vox

Vox

Speec

Phanto

Off

Off

On

LBB 19 90/00

Plena

Max. o

115-23

S/N.

Voice Alarm d outp ut pow

Contro

60W

8900

W

199 00 ller 001

Design

0/60H

The N etherla & Qua lity nds

N663

USB h filter m pow

115V~

230V~

Line fu

T6.3L2

se

50V fo

LBB199

T10L2 50V fo

Remote r115V

Contro r230

V AC

AC l Panel

Appara tus de

Conne cted fo livered r 230V

Firema n’s pan

Power

Rated input p ower:7

60VA

On

Digital

Messa ge

Monito

Speake ring

Router

Warni

This ap ng paratu s mu st be earthe

LBB1990/00

Charger

24

VDC

+

figure 3.18: Connecting a back-up power supply figure 3.17: Connecting the mains cord

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Configuration en | 27

4 Configuration

4.1 Introduction

A basic system is configured using the DIP switches and volume controls on the rear of the voice alarm controller and the DIP switches on the bottom of the call station.

4.3 Monitor

If the Monitor switch (see figure 4.1) is in the ON

position, the internal monitoring loudspeaker of the voice alarm controller is switched on. The volume of the monitoring loudspeaker is set with the Monitoring

Speaker

volume control (see figure 2.3, no. 36).

4.2.1

Introduction

The system settings are configured using DIP switches

on the rear of the voice alarm controller (see figure 4.1).

By default, all switches are in the OFF position.

Monitor

APR mode

Supervision

2ch operation

Reserved

Off

On

figure 4.1: System settings DIP switches

If the APR mode switch (see figure 4.1) is in the ON

position, the system is in the Asian-Pacific Region (APR) mode. In APR mode, the system operates according to the emergency standards of the Asian-Pacific Region.

For a basic system, the differences between normal operation and the APR mode are:

When the emergency button (see figure 2.3, no. 12)

is pushed on the front of the voice alarm controller, an alarm message is automatically started. This message is automatically repeated.

• In the APR mode the red LED, which during normal operation indicates that the zone is selected for an

emergency call (see figure 2.3, no. 5), does not work.

• In the APR mode the green LED, which during normal operation indicates that a business call is

running in the zone (see figure 2.3, no. 5), indicates

that an emergency call is running in the zone.

table 4.1: System settings DIP switches

DIP switch Description

Monitor

APR mode

Reserved

Switches the monitoring loudspeaker on (ON) and off (OFF).

See section 4.3.

Switches the Asian Pacific Region mode on (ON) and off (OFF). See

Supervision

section 4.4.

Switches supervision on (ON) and

off (OFF). See section 4.5.

2ch operation Switches 2-channel operation on

(ON) and off (OFF). See section

4.5.11.

Reserved. This DIP switch must always be in the OFF position.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Configuration en | 28

4.5 Supervision

4.5.1

Introduction

If the Supervision switch (see figure 4.1) is in the ON

position, supervision is enabled. If it is in the OFF position, supervision is disabled.

Note

Supervision is only necessary for systems that have to comply to the IEC60849 evacuation standard. If the system does not have to comply to this standard, leave the switch in the OFF position.

If the Supervision switch is in the OFF position, the

Disabled

indicator on the front panel of the voice alarm

controller is lit (see figure 4.2) to indicate that

supervision is switched off.

0 dB

-6dB

-20dB

Fault Indicators

Processor reset

Network

Call/EMG

Music/Spare

Ground short

Input

Mains

Battery

Message

EMG mic

RCP

Router

A

Disabled

B

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

4.5.2

Overview

The supervised functions can be configured with a PC and the configuration software. To basic systems, the default settings apply (see table 4.2).

table 4.2: Default supervision settings

Supervision of:

Processor

Default setting

On. See section 4.5.3.

Network

Messages

Off.

On. See section 4.5.4.

Line supervision

On. See section 4.5.5.

Emergency microphone

On. See section 4.5.6.

Input contacts Off.

Mains power

Battery power

On. See section 4.5.7.

On. See section 4.5.8.

Internal power amplifier

On. See section 4.5.9.

VOX 20 kHz input Off.

External power amplifier Depends on position of the 2ch operation switch.

See section 4.5.11.

Note

See section 5.7 for information about faults.

figure 4.2: Disabled indicator

4.5.3

Processor supervision

If supervision is enabled (see section 4.5.1), the

processor of the voice alarm controller is supervised by a watchdog. If the watchdog triggers, the Processor reset indicator on the front panel of the voice alarm controller is lit. Then, the program memory is checked and the processor resumes operation within 10 seconds.

The indicator remains on until the fault is acknowledged and reset.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Configuration en | 29

4.5.4

Message supervision

If supervision is enabled (see section 4.5.1), the internal

message manager of the voice alarm controller is supervised. This message supervision consists of supervision of the wave player using a check-sum and supervision of the audio path using a pilot tone.

4.5.6

Emergency microphone

If supervision is enabled (see section 4.5.1), the audio

path and the PTT switch of the emergency microphone are monitored from the capsule to the connection with the voice alarm controller.

4.5.5

Line supervision

4.5.5.1

Introduction

If supervision is enabled (see section 4.5.1), all

loudspeaker lines are supervised. Line supervision consists of:

Short-circuit supervision (see section 4.5.5.2).

Impedance supervision (see section 4.5.5.3).

Short-to-ground supervision (see section 4.5.5.4).

4.5.5.2

Short-circuit supervision

The voice alarm controller continuously monitors all loudspeaker lines in the system for short-circuits. If a short-circuit is detected, the line output of the short-circuited line is isolated and shut down within 200 ms. The system will remain operational. If the line is dual-redundant connected (A and B) the short-circuited line remains operational as well.

4.5.7

Mains power supervision

If supervision is enabled (see section 4.5.1), the

availability of the mains power is supervised.

4.5.8

Battery supervision

If supervision is enabled (see section 4.5.1), the

availability of the back-up power is supervised.

4.5.9

Internal power amplifier supervision

If supervision is enabled, the internal power amplifier of the voice alarm controller is supervised. The function of this power amplifier depends on the position of the 2ch operation

switch (see section 4.5.11).

table 4.3: Internal power amplifier functions

Operational mode Function

1-channel

2-channel

BGM/Call power amplifier

BGM/Spare power amplifier

4.5.5.3

Impedance supervision

If supervision is enabled, the voice alarm controller measures the impedance of all loudspeaker lines once every 90 seconds. The reference values for impedance supervision are stored in the voice alarm controller

during the system calibration (see section 5.3). If a

difference of > 15% is detected between the measured line impedance and its reference value, the line is considered faulty.

4.5.10 External power amplifier supervision

If supervision is enabled and the 2ch operation switch

(see section 4.5.11) is in the ON position, the external

power amplifier is supervised. In 2-channel mode, the external power amplifier is always the call power amplifier.

Note

For a correct impedance supervision, connect

loudspeakers as described in section 3.10.

4.5.5.4

Short-to-ground supervision

If supervision is enabled, the voice alarm controller continuously monitors all loudspeaker lines in the system for short-to-ground situations. If a leakage current > 30 + 15 mA is detected in a line, the line is considered faulty.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Configuration en | 30

4.5.11 1 channel and 2 channel operation

4.5.11.1

Introduction

If the 2ch operation switch (see figure 4.1) is in the ON

position, the voice alarm controller operates in the

2-channel mode. If the 2ch operation switch is in the

OFF position, the voice alarm controller operates in the

1-channel mode.

4.6.1

Introduction

The type of source that is connected to the mic/line input with VOX functionality is set using the Mic/Line switch on the rear of the voice alarm controller (see

figure 4.3).

• If the source is a microphone, put the switch in the

Mic

position.

• If the source is a line-level source, put the switch in the Line position.

4.5.11.2

1-channel mode

In the 1-channel mode, all calls and BGM are amplified by the internal power amplifier of the voice alarm controller. If desired, an external power amplifier can

be connected for spare switching (see section 3.9). In 1-

channel mode, all calls will interrupt the BGM. The

external power amplifier is not supervised (see section

4.5.10).

Vox

Speech filter

Phantom power

Off

Mic/Line

On

figure 4.3: VOX input source switch table 4.4: 1-channel mode

Amplifier Function

Internal

External

BGM/Call power amplifier

Not connected/Spare power amplifier

The mic/line input with VOX functionality is configured using DIP switches on the rear of the voice

alarm controller (see figure 4.4). By default, all switches

are in the OFF position.

4.5.11.3

2-channel mode

In the 2-channel mode, the BGM is amplified by the internal power amplifier of the voice alarm controller.

The calls are amplified by the external power amplifier, which is connected to the voice alarm controller

(see section 3.9). If the external power amplifier is

faulty, the calls are amplified by the internal power amplifier. In 2-channel mode, calls do not interrupt the

BGM. Both the internal power amplifier and the

external power amplifier are supervised (see section

4.5.10).

Mic/Line

figure 4.4: VOX settings

Vox

Speech filter

Phantom power

Off

On

The settings that can be made using the DIP switches are explained in a table on the rear of the voice alarm

controller (see figure 4.5).

table 4.5: 2-channel mode

Amplifier Function

Internal

External

BGM/Spare power amplifier

Call power amplifier

Off

1 VOX activate by mic.

2 Speech filter

3 Phantom power Off

figure 4.5: VOX settings table

On

VOX activate by VOX Switch

Flat

Phantom power On

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Configuration en | 31

The volume of the mic/line input with VOX functionality is set with the VOX volume control (see

figure 4.6).

4.7.1

Introduction

The call stations are configured using the DIP switch at

the bottom (see figure 4.7).

Vox

Speech filter

Phantom power

Off

Mic/Line

On

figure 4.6: VOX volume control

4.6.2

Vox

If the Vox switch is in the OFF position, the input is activated when the voltage of the signal of the source is above the specified threshold. If the Vox switch is in the

ON

position, the input is activated when the VOX

Switch

trigger input is closed (see also section 3.13).

4.6.3

Speech filter

If the Speech filter switch is in the OFF position, a speech filter is activated for the mic/line input with

VOX functionality. The speech filter improves the speech intelligibility by cutting off the lower frequencies.

figure 4.7: Call station DIP switches table 4.6: Call station DIP switches

DIP switch Description

1, 2, 3, 4

5, 6

7

8

Set the ID of the call station. See

section 4.7.2

Set the sensitivity of the call station.

See section 4.7.3.

Switches the speech filter on (ON)

and off (OFF). See section 4.7.4.

Switches termination on (ON) and

off (OFF). See section 4.7.5.

4.6.4

Phantom power

If the Phantom power switch is in the ON position, a phantom power supply is activated. This switch only has to be put in the ON position if the source is a microphone that must receive phantom power. If the source is not a microphone or if the microphone does not accept phantom power, leave the switch in the OFF position.

4.7.2

Call station ID

The ID of the call station is set using switches 1 to 4.

Since a basic system can contain only 1 call station, the

ID of this call station is 1. This is accomplished by leaving the DIP switches 1 to 4 in the default OFF position.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Configuration

4.7.3

Sensitivity

The sensitivity of the call station is set using switches 5

and 6 (see table 4.7).

table 4.7: Call station sensitivity

Sensitivity Switch 5

-15 dB

0 dB

6 dB

Reserved

OFF

OFF

ON

ON

Switch 6

OFF

ON

OFF

ON

4.7.4

Speech filter

If switch 7 is in the ON position, a speech filter is activated for the call station. The speech filter improves the speech intelligibility by cutting off the lower frequencies.

4.7.5

Termination

Switch 8 must always be in the ON position, since basic systems contain only 1 call station.

en | 32

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 33

5 Operation

Note

It is assumed that the APR mode switch (see

section 4.4) is in the OFF position.

Put the Power switch on the rear of the voice alarm controller (see figure 5.1) in the I position.

115V~ 230V~

Put the Power switch of the voice alarm controller (see figure 5.1) in the O position.

5.3 Calibration

Calibration is necessary for a correct loudspeaker line

impedance supervision (see section 4.5.5.3). To calibrate

the voice alarm controller, push the calibration switch

(see figure 2.3, no. 24). The system must be calibrated:

• When the voice alarm controller is switched on for the first time.

• After the connected loudspeakers are changed.

• After loudspeakers have been added.

• After the settings of the connected loudspeakers have been changed.

Apparatus delivered

Connected for 230V~

figure 5.1: Power switch

Power

If mains power or back-up power is available, the power indicator on the front of the voice alarm controller is lit

(see figure 5.2). If the basic system contains a call

station, the power indicator of the call station is also lit

(see figure 2.5, no. 1).

5.4.1

Introduction

The background music (BGM) is controlled using the

BGM controls on the front of the voice alarm controller

(see figure 2.3). Proceed as follows to route BGM:

1 Select the BGM source (see section 5.4.2).

2 Select the zones (see section 5.4.3).

0 dB

-6dB

-20dB

Fault Indicators

Processor reset

Network

Call/EMG

Music/Spare

Ground short

Input

Mains

Battery

Message

EMG mic

RCP

Router

A

Disabled

B

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

5.4.2

Select BGM source

Select the BGM source with the Select button (see

figure 5.3). A green LED indicates the source that is

selected.

• If the source is a CD player or a tuner that is

connected to the CD/Tuner input (see section 3.7),

choose CD/Tuner.

• If the source is an auxiliary source that is connected

to the Aux input (see section 3.7), choose Aux.

figure 5.2: Power indicator

Select

CD/Tuner Aux

Zone select

Note

When the system is switched on for the first time and supervision is enabled, calibrate the

system (see section 5.3).

+

+

0

figure 5.3: BGM source selector

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 34

5.4.3

Select zones

The BGM is distributed to the zones with the Zone select

buttons (see figure 5.4). A green LED indicates

the zones to which BGM is distributed.

• If the Zone select indicator is off, no BGM is distributed to the zone. Push the Zone select button to distribute the BGM to the zone.

• If the Zone select indicator is on, BGM is distributed to the zone. Push the Zone select button to stop distributing the BGM to the zone.

5.4.5

Adjust frequencies

The voice alarm controller has two rotary knobs to

adjust the sound of the BGM (see figure 5.6).

• Use the upper rotary knob to adjust the treble or high frequency content of the BGM.

• Use the lower rotary knob to adjust the bass or low frequency content of the BGM.

Select

CD/Tuner Aux

Zone select

Select

CD/Tuner Aux

Zone select

+

+

+ 0

figure 5.6: BGM tone controls

+ 0

figure 5.4: BGM zone selectors

5.4.4

Adjust volume

The voice alarm controller has two types of controls to

adjust the BGM volume (see figure 5.5). The overall

(maximum) volume of the BGM source is set with the master volume control, which is located below the BGM

source selector (Select button, see figure 5.3). Per zone,

the local volume can be adjusted with the zone volume switches, which are located below the zone selection

buttons (Zone select, see figure 5.4).

Select

CD/Tuner Aux

Zone select

+

+

0

figure 5.5: BGM volume controls

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 35

5.5.1

Introduction

Business calls can only be distributed with call stations.

It is not possible to use the hand-held emergency microphone to distribute business calls. Proceed as follows to distribute a business call:

1 Select the zones (see section 5.5.2).

2 Make the announcement (see section 5.5.3).

5.5.3

Make the announcement

Push the push-to-talk (PTT) button of the call station to

make an announcement (see figure 5.8). The call is only distributed to the selected zones (see section 5.5.2).

Plena

5.5.2

Select zones

Select the zones to which the business call must be distributed with the zone selection buttons on the call station (see figure 5.7). A green LED indicates the zones to which the business call is distributed.

• If the indicator of a button is off, the zone is not selected. Push the button to select the zone.

• If the indicator of a button is on, the zone is selected.

Push the button to deselect the zone.

Plena

Z4

Z5

Z6

Z1-Z6

Z1

Z2

Z3

figure 5.8: PTT button and indicators

The LEDs above the PTT button provide information

about the status of the call station (see table 5.1).

table 5.1: Call station status indicators

Indicator

Green

Yellow

Red

Description

PTT button is pushed.

Fault in the system.

System is in emergency state. The call station is disabled.

figure 5.7: Zone select buttons

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 36

5.6.1

Introduction

Emergency calls can only be distributed when the

system is in the emergency state. See section 5.6.2 for

information about entering the emergency state. In the emergency state, it is possible to distribute the following emergency calls:

• Live speech with the emergency microphone of the

voice alarm controller (see section 5.6.5).

5.6.3

Acknowledge the emergency state

The beeper can be switched off by acknowledging the

emergency state with the EMG Ack button (see figure

5.10).

Fault

Ack

Reset

EMG

Zone select

Zone1 Zone2

Note

It is not possible to distribute chimes or speech with the call station when the system is in the emergency state, because the call station is disabled automatically at the moment that the system enters the emergency state.

figure 5.10: EMG Ack button

5.6.4

Exit the emergency state

Exit (reset) the emergency state by pushing the EMG

Reset

button (see figure 5.11). In order to reset the emergency state, it first must be acknowledged (see

section 5.6.3).

The default alert message (see section 5.6.6).

The default alarm message (see section 5.6.7).

5.6.2

Enter the emergency state

To enter the emergency state, push the emergency button on the front of the voice alarm controller (see

figure 5.9). The red LED that is integrated in the switch

lights.

Fault EMG

Ack

Zone select

Reset

figure 5.11: EMG Reset button

Zone1 Zone2

5.6.5

Distribute live speech

Alert message All call

EMG mic

Alarm message

Indicator test

5.6.5.1

Introduction

Proceed as follows to distribute live speech:

1 Select zones (see section 5.6.5.2).

2 Make announcement (see section 5.6.5.3).

figure 5.9: Emergency button

At the moment the emergency state is entered, a beeper starts and the EMG status output contact is closed.

Note

See section 5.6.4 for information about exiting

the emergency state.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 37

5.6.5.2

Select zones

Select the zones to which the live speech must be distributed with the Zone select buttons on the front of the voice alarm controller (see figure 5.12). A red LED indicates the zones to which the live speech is distributed.

• If the indicator of a Zone select button is off, the zone is not selected. Push the button to select the zone.

• If the indicator of a Zone select button is on, the zone is selected. Push the button to deselect the zone.

5.6.5.3

Make the announcement

Push the push-to-talk (PTT) button of the emergency microphone to make an announcement (see figure 5.14).

The live speech is only distributed to the selected zones

(see section 5.5.2). At the moment the PTT button of the

emergency microphone is pushed:

• The red EMG mic indicator is lit (see figure 5.15).

• If they are currently distributed, the default alert message and default alarm message are stopped.

Note

If no additional action is taken within 10 seconds after the last Zone select button has been pushed (for example closing the PTT switch), the zone selection is cancelled.

Note

If no zones have been selected, the live speech is automatically distributed to all zones in the system.

Fault

EMG

Ack

Zone select

Reset

figure 5.12: Zone select buttons

Zone1 Zone2

To select all zones, push the All call buttons on the front panel of the voice alarm controller (see figure 5.13).

Alert message

EMG mic

Alarm message

All call

Indicator test

figure 5.14: Emergency microphone

Alert message

EMG mic

Alarm message

All call

Indicator test

figure 5.13: All call button figure 5.15: Emergency microphone indicator

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 38

5.6.6

Distribute the alert message

To select all zones, push the All call button on the front panel of the voice alarm controller (see figure 5.17)

5.6.6.1

Introduction

Proceed as follows to distribute the default alert message:

• Select the zones (see section 5.6.6.2).

• Start the alert message (see section 5.6.6.3).

Alert message

Alarm message

All call

Indicator test

EMG mic

5.6.6.2

Select zones

Select the zones to which the default alert message must be distributed with the Zone select buttons on the front of the voice alarm controller (see figure 5.12). A red

LED indicates the zones to which the default alert message is distributed.

• If the indicator of a Zone select button is off, the zone is not selected. Push the button to select the zone.

• If the indicator of a Zone select button is on, the zone is selected. Push the button to deselect the zone.

Note

If no additional action is taken within 10 seconds after the last Zone select button has been pushed (for example pushing the Alert message button), the zone selection is cancelled.

figure 5.17: All call button

5.6.6.3

Start the alert message

Push the Alert message button to distribute the message to distribute the default alert message (see figure 5.18).

The message is only distributed to the selected zones

(see 5.6.6.2).

• If the red Alert message indicator is off, the alert message is not distributed. Push the Alert message button to distribute the default alert message.

• If the red Alert message indicator is on, the message is distributed. Push the Alert message button to stop distributing the default alert message.

Alert message All call

Indicator test

EMG mic

Alarm message

Fault EMG

Ack

Zone select

Reset

figure 5.16: Zone select buttons

Zone1 Zone2

figure 5.18: Alert message button

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation en | 39

5.6.7

Distribute the alarm message

Distributing the default alarm message is similar to

distributing the default alert message (see section 5.6.6).

Push the Alarm message button instead of the Alert message button (see figure 5.19).

The following buttons also acknowledge the fault state and stop the beeper:

• Alert button

Alarm

button

• PTT button of the emergency microphone

EMG mic

Alert message

Alarm message

All call

Indicator test

figure 5.19: Alarm message button

5.7.3

Reset the fault state

Reset the fault state by pushing the Fault Reset button

(see figure 5.21). In order to reset the fault state, it first

must be acknowledged (see section 5.7.2). When the

Fault Reset

button is pushed, the fault indicators are switched off and the status of the system is checked.

• If the fault is not resolved, the fault indicators are switched on again. The beeper remains off. It is only switched on if a new fault occurs or if the resolved fault occurs again.

• If the fault is resolved, the fault indicators remain off.

5.7.1

Introduction

If a supervised function fails, the voice alarm controller enters the fault state and:

• Starts a beeper. The beeper is switched off when the

fault is acknowledged (see section 5.7.2).

• Closes the Fault Status NO output contact. This status output contact is opened again when the fault

is reset (see section 5.7.3).

• Lights a fault indicator on the front panel that

indicates the source of the fault (see section 5.7.4).

The indicator is switched off when the fault is reset

(see section 5.7.3).

5.7.2

Acknowledge the fault state

The beeper can be switched off by acknowledging the

fault state with the Fault Ack button (see figure 5.20).

Fault EMG

Ack

Zone select

Reset

figure 5.21: Fault Reset button

Zone1 Zone2

Fault EMG

Ack

Reset

figure 5.20: Fault Ack button

Zone select

Zone1 Zone2

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation

5.7.4

Fault indicators

The voice alarm controller has two types of fault

indicators: system fault indicators (see figure 5.22) and loudspeaker line fault indicators (see figure 5.23). They

provide information about failing system functions that are supervised (see table 5.2). If a system fault is persistent, contact your dealer.

0 dB

-6dB

-20dB

Fault Indicators

Processor reset

Network

Call/EMG

Music/Spare

Ground short

Input

Mains

Battery

Message

EMG mic

RCP

Router

A

Disabled

B

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

figure 5.22: System fault indicators

The loudspeaker line indicators provide information about failing loudspeaker lines. They indicate short-

circuit (see section 4.5.5.2) and impedance supervision

(see section 4.5.5.3) faults. If a loudspeaker line indicator

lights, check the wiring of the indicated loudspeaker line and try to solve the fault. If it not possible to determine the fault, contact your dealer.

0 dB

-6dB

-20dB

Fault Indicators

Processor reset

Network

Call/EMG

Music/Spare

Ground short

Input

Mains

Battery

Message

EMG mic

RCP

Router

A

Disabled

B

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

figure 5.23: Loudspeaker line indicators

If supervision is disabled (see section 4.5), the fault

indicators do not function and the Disabled indicator is

lit (see figure 5.24).

0 dB

-6dB

-20dB

Fault Indicators

Processor reset

Network

Call/EMG

Music/Spare

Ground short

Input

figure 5.24: Disabled indicator

Mains

Battery

Message

EMG mic

RCP

Router

A

Disabled

B

Zone1

Zone2

Zone3

Zone4

Zone5

Zone6

The availability of the indicators can be tested with the

Indicator test

button (see figure 2.3, no. 11).

Bosch Security Systems | 2005-04 | 9922 141 10364en en | 40

Plena Voice Alarm System | Basic System Manual | Operation en | 41

table 5.2: System fault indicators

Indicator

Processor reset A processor reset is detected.

Network

Call/EMG

Music/Spare

Ground short

Input

Mains

Battery

Message

EMG mic

RCP

Router

Description

A network fault is detected.

Recommended action

Switch the voice alarm controller off and on again.

Contact your dealer.

Additional information

See section 4.5.3.

This fault should not occur, since this type of supervision

is disabled (see section 4.5)

See section 3.9 and section

4.5.11.

In 1-channel mode:

The internal power amplifier of the voice alarm controller failed.

In 1-channel mode:

Switch the voice alarm controller off and on again.

In 2-channel mode:

The external power amplifier failed.

In 1-channel mode:

The external power amplifier failed.

In 2-channel mode:

Switch the external power amplifier off and on again.

In 1-channel mode:

Switch the external power amplifier off and on again.

See section 3.9 and section

4.5.11.

In 2-channel mode:

The internal power amplifier failed.

A short-to-ground fault in the loudspeaker line cabling is detected.

An input contact fault is detected.

A router fault is detected.

In 2- channel mode:

Switch the voice alarm controller off and on again.

Check all loudspeaker lines for short-to-ground situations.

Contact your dealer.

A mains power failure is detected.

A remote control panel fault is detected.

Check the mains power connection of the voice alarm controller and the mains power availability.

Check the back-up power supply connection of the

A back-up power failure is detected.

voice alarm controller and the back-up power availability.

A message fault is detected.

Switch the voice alarm

A emergency microphone fault is detected.

controller off and on again.

Check the emergency microphone. If necessary, replace it.

Contact your dealer.

Contact your dealer.

See section 3.10 and section

4.5.5.4

This fault should not occur, since this type of supervision

is disabled (see section 4.5).

See section 3.15.2 and

section 4.5.7.

See section 3.15.3 and

section 4.5.8.

See section 4.5.4.

See section 3.6 and section

4.5.6.

This fault should not occur, since this type of supervision

is disabled (see section 4.5).

This fault should not occur, since this type of supervision

is disabled (see section 4.5).

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Operation

Intentionally left blank en | 42

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Technical Data en | 43

6 Technical data

6.1 LBB1956/00

6.1.1

Electrical

Voltage range:

24 V(DC), +10%/-20%, supplied by LBB1990/00 or external power source.

Current consumption:

< 30 mA

6.1.2

Performance

Nominal sensitivity:

85 dB SPL (gain preset 0 dB)

Nominal output level:

355 mV

Maximum input sound level:

110 dB SPL

Gain preset:

+6/0/-15 dB

Limiter threshold:

2 V

Compression ratio limiter:

20:1

Distortion:

< 0.6% (nominal input)

< 5% (maximum input)

Equivalent input noise level:

25 dB SPL(A)

Frequency response:

100 Hz — 16 kHz

Speech filter:

— 3 dB @ 500 Hz, high-pass, 6 dB/oct

Output impedance:

200

6.1.3

Interconnection

Type:

2x redundant RJ45 sockets to connect the call station to the voice alarm controller with Cat-5 Ethernet cables.

6.1.4

Environmental conditions

Operating temperature range:

-10 to +55 °C

Storage temperature range:

-40 to +70 °C

Relative humidity:

< 95%

6.1.5

General

EMC emission:

According to EN55103-1

EMC immunity:

According to EN55103-2

Dimensions:

40 x 100 x 235 mm (base)

390 mm stem length (with microphone)

Weight: approx. 1 kg

6.2 LBB1990/00

6.2.1

Electrical

Mains voltage:

230/115 V(AC), ± 10%, 50/60 Hz

Mains current:

0.3 A (system idle)

4.0 A (maximum load)

Max. mains inrush current:

6.3 A (for mains voltage of 220 — 240 V)

10 A (for mains voltage of 100 — 120 V)

Battery voltage:

20.0 to 26.5 V(DC)

Battery current:

0.9 A (system idle)

14 A (maximum load)

Note

Maximum load means meaximum power out, maximum load 24 V(DC) out and maximum number of call stations.

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Technical Data

6.2.2

Message manager

Data format:

WAV-file, 16-bit PCM, mono

Supported sample rates (fs):

24 kHz, 22.05 kHz, 16 kHz,

12 kHz, 11.025 kHz, 8 kHz

Frequency response:

@ fs = 24 kHz, 100 Hz — 11 kHz (+1/-3 dB)

@ fs = 22.05 kHz, 100 Hz — 10 kHz (+1/-3 dB)

@ fs = 16 kHz, 100 Hz — 7.3 kHz (+1/- 3 dB)

@ fs = 12 kHz, 100 Hz — 5.5 kHz (+1/-3 dB)

@ fs = 11.025 kHz, 100 Hz — 5 kHz (+1/-3 dB)

@ fs = 8 kHz, 100 Hz — 3.6 kHz (+1/-3 dB)

Distortion:

< 0.1% @ 1 kHz

Signal-to-noise ratio (flat at max. volume):

> 80 dB

Memory capacity:

64 Mbit Flash

Recording/playback time:

1000 s @ fs = 8 kHz to 333 s @ fs = 24 kHz

Number of messages: max. 254 wave files

Supervision EEPROM: continuous checksum control

Supervision DAC:

1 Hz pilot tone

Data retention time:

> 10 years

6.2.3

Internal power amplifier

Rated output power:

240 W

Frequency response:

50 Hz — 20 kHz (+1/-3 dB, @ -10 dB ref. rated output)

Distortion:

< 1% @ rated output power, 1 kHz

Signal-to-noise ratio (flat at max. volume):

> 85 dB

Supervision:

20 kHz pilot tone

Outputs:

70, 100 V screw terminal, 100 V call out

6.2.4

Interconnection

LBB1956/00:

Redundant RJ45 sockets, CAN bus max. 8 call stations

LBB1992/00:

RJ45 socket, CAN bus max. 2 routers

PC:

USB 2.0 (USB 1.1 compatible)

External power amplifier:

3-pin XLR and screw terminals, max. 5 A max. rated output 1000 W

6.2.5

Loudspeaker outputs

Type:

Screw terminals

Number of zones:

6

Number of loudspeaker lines:

12 (2 per zone)

Signal-to-noise ratio (flat at max. volume):

> 85 dB

Line voltage:

100 V

6.2.6

Overrides

Type:

3-wire or 4-wire on screw terminals

Voltage:

24 V(DC) for 4-wire, if selected

Current: total 0.8 A

6.2.7

Trigger outputs

Type:

Screw terminals

Voltage:

Floating, max. 250 V

Current: max. 0.5 A en | 44

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Technical Data

6.2.8

Trigger inputs/24 V DC out

Trigger voltage:

< 24 V

Type

Momentary or latching

Normally opened (default) or normally closed

Emergency input supervision:

10 k

+ 10 k

series and parallel resistors

24 V DC out:

24 V(DC), max. 0.8 A

VOX switch:

Normally opened

6.2.9

Mic/line input with VOX functionality

Type:

3-pin XLR, 6.3 mm jack socket, balanced

Sensitivity:

1 mV +1/-3 dB (mic), 1 V +1/-3 dB (line)

Impedance:

> 10 k

VOX threshold:

500 µV (mic), 500 mV (line)

6.2.10 BGM

Type:

Cinch, stereo converted to mono

Nominal input level:

500 mV

6.2.11 Line out

Type:

3-pin XLR, 6.3 mm jack socket, balanced

Nominal output level:

1 V

Maximum output level:

1 V

6.2.12 External power amplifier

Type:

3-pin XLR and screw terminals

Controller output/External power amplifier input voltage:

1 V

Controller input/External power amplifier output voltage:

100 V

6.2.13 Environmental conditions

Operating temperature range:

-10 to +55 °C

Storage temperature range:

-40 to +70 °C

Relative humidity:

< 95%

6.2.14 General

EMC emission:

According to EN55103-1

EMC immunity:

According to EN55103-2

Dimensions:

19” wide, 3 U high, 360 mm deep

(leave 50 mm for connections)

19” mounting brackets: included

Weight: approx. 20 kg en | 45

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Technical Data

Intentionally left blank.

en | 46

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Glossary en | 47

7 Glossary

A

APR mode

Asian-Pacific Region mode.

B

BGM

Background music.

Business call

Live announcement that is made when the system is in the normal state. Business calls can only be made with a call station.

E

Emergency call

Live speech, alert message or alarm message that is distributed in the emergency state. Emergency calls can only be made with the voice alarm controller.

Emergency state

Emergency calls can only be distributed in the emergency state. This state is entered by pushing the red emergency button on the front panel of the voice alarm controller. At the moment the emergency state is entered, a beeper starts. Simultaneously, the default alert message and the default alarm message are distributed to all zones in the system.

F

Fault state

If a supervised function fails, the system automatically enters the fault state. It starts a beeper, de-energizes the Fault Status output contact and lights an indicator on the front panel of the voice alarm controller.

L

LED

Light Emitting Diode. Electronic component that frequently is used as indicator.

P

PC

Personal Computer.

PDF

Portable Document Format. Type of file.

Praesideo

Digital public address and emergency sound system of Bosch Security Systems.

PTT button

Push-to-talk button. A button that starts the actual call.

U

USB

Universal Serial Bus. Type of bus that is used to connect equipment to PCs.

V

VOX

Voice-activated. The voice alarm controller has one voice-activated input to connect an additional emergency microphone or to interface with another emergency sound system (e.g. a Praesideo system).

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Glossary

Intentionally left blank.

en | 48

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Product Index

8 Product Index

en | 49

table 8.1: Product index

Code Reference

LBB1990/00

LBB1992/00

LBB1994/00

LBB1995/00

LBB1996/00

LBB1997/00

LBB1998/00

LBB1999/00

LBB1956/00

LBB1957/00

Controller

Router

Logger

Fireman’s panel

Remote control

Remote control kit

Remote control extension

Description

Main unit

Slave unit

Event logging unit

Remote control with basic functionality

Remote control for controller

Same as remote control, but with rugged connectors

Remote control extension for router

Remote control extension kit Same as remote control extension, but with rugged connectors

Call station Based on existing LBB1946 with 6 zone keys and all call

Call station keypad Call station keypad extension with 7 zone keys

Bosch Security Systems | 2005-04 | 9922 141 10364en

Plena Voice Alarm System | Basic System Manual | Product Index

Intentionally left blank.

en | 50

Bosch Security Systems | 2005-04 | 9922 141 10364en

For more information visit www.boschsecuritysystems.com

© Bosch Security Systems B.V.

Data subject to change without notice

2005-04 | 9922 141 10364en

background image

Система речевого и аварийного
оповещения Plena

Plena_VAS

ru

Руководство по установке и эксплуатации

Понравилась статья? Поделить с друзьями:
  • Pleervox plv pl uni инструкция
  • Pipamperon инструкция по применению 40
  • Plc адаптер rp 501 1 инструкция
  • Pioneer магнитола в машину инструкция
  • Pioneer магнитола mosfet 50wx4 инструкция по применению